(!) Since support from Microsoft will end on January 14th, 2020, Windows 7 will be excluded from the recommended environment from December 15th, 2019 on this site. Vì lý do Microsoft kết thúc hỗ trợ cho Windows 7 vào ngày 14/01/2020, Windows 7 sẽ là hệ điều hành không được khuyến khích sử dụng với trang web này từ ngày 15/12/2019.
Select part number to Order Now/ Add to Cart
Power supply unit for iQ-R series available.
R61P external appearance
R61P dimensional outline drawing
(Unit: mm)
Input Power Supply Voltage | 100 to 240 V AC (85 to 264 V AC) | ||
---|---|---|---|
Input Frequency | 50/60 Hz ±5% | ||
Input Voltage Strain Factor | Within 5% | ||
Input Maximum Apparent Power | 130 VA | ||
Inrush Current | 20 A within 8 ms | ||
Rated Output Current | 5 V DC | 6.5 A | |
Excess Current Protection | 5 V DC | 7.1 A or more | |
Excess Voltage Protection | 5 V DC | 5.5 to 6.5 V | |
Efficiency | 76% or more | ||
Allowable Momentary Power Loss Duration | Within 20 ms | ||
Withstand Voltage | 2,300 Vrms AC / 1 minute (altitude 0 to 2,000 m) between all inputs / LG at once and all outputs / FG at once | ||
Insulation Resistance | Between all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter | ||
Fuse | Built-in (cannot be replaced by the user) | ||
Contact Output Part | Applications | ERR Contact | |
Rated Switching Voltage/Current | 24 V DC, 0.5 A | ||
Minimum Switching Load | 5 V DC 1 mA | ||
Response Time | OFF→ON | 10 ms or less | |
ON→OFF | 12 ms or less | ||
Lifespan | Mechanical | 20,000,000 operations or more | |
Electrical | Rated switching voltage/current 100,000 times or more | ||
Surge Protector | No | ||
Fuse | No | ||
External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) | |
Width (W) | 54.6 mm | ||
Depth (D) | 110 mm | ||
Mass | 0.41 kg |
(Unit: mm)
R62P/R63P/R64P dimensional outline drawing
Input Power Supply Voltage | 100 to 240 V AC (85 to 264 V AC) | ||
---|---|---|---|
Input Frequency | 50/60 Hz ±5% | ||
Input Voltage Strain Factor | Within 5% | ||
Input Maximum Apparent Power | 120 VA | ||
Inrush Current | 20 A within 8 ms | ||
Rated Output Current | 5 V DC | 3.5 A | |
24 V DC | 0.6 A | ||
Excess Current Protection | 5 V DC | 3.8 A or more | |
24 V DC | 0.66 A or more | ||
Excess Voltage Protection | 5 V DC | 5.5 to 6.5 V | |
Efficiency | 76% or more | ||
Allowable Momentary Power Loss Duration | Within 20 ms | ||
Withstand Voltage | 2,300 Vrms AC / 1 minute (altitude 0 to 2,000 m) between all inputs / LG at once and all outputs / FG at once | ||
Insulation Resistance | Between all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter | ||
Fuse | Built-in (cannot be replaced by the user) | ||
Contact Output Part | Applications | ERR Contact | |
Rated Switching Voltage/Current | 24 V DC, 0.5 A | ||
Minimum Switching Load | 5 V DC 1 mA | ||
Response Time | OFF→ON | 10 ms or less | |
ON→OFF | 12 ms or less | ||
Lifespan | Mechanical | 20,000,000 operations or more | |
Electrical | Rated switching voltage/current 100,000 times or more | ||
Surge Protector | No | ||
Fuse | No | ||
External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) | |
Width (W) | 54.6 mm | ||
Depth (D) | 110 mm | ||
Mass | 0.45 kg |
Input Power Supply Voltage | 24 V DC (15.6 to 31.2 V DC) | ||
---|---|---|---|
Input Maximum Power | 50 W | ||
Inrush Current | 100 A within 1 ms | ||
Rated Output Current | 5 V DC | 6.5 A | |
Excess Current Protection | 5 V DC | 7.1 A or more | |
Excess Voltage Protection | 5 V DC | 5.5 to 6.5 V | |
Efficiency | 70% or more | ||
Allowable Momentary Power Loss Duration | Within 10 ms | ||
Withstand Voltage | 50 V AC / 1 minute (altitude 0 to 2,000 m) Between primary side and 5 V DC | ||
Insulation Resistance | Between all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter | ||
Fuse | Built-in (cannot be replaced by the user) | ||
Contact Output Part | Applications | ERR Contact | |
Rated Switching Voltage/Current | 24 V DC, 0.5 A | ||
Minimum Switching Load | 5 V DC 1 mA | ||
Response Time | OFF→ON | 10 ms or less | |
ON→OFF | 12 ms or less | ||
Lifespan | Mechanical | 20,000,000 operations or more | |
Electrical | Rated switching voltage/current 100,000 times or more | ||
Surge Protector | No | ||
Fuse | No | ||
External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) | |
Width (W) | 54.6 mm | ||
Depth (D) | 110 mm | ||
Mass | 0.41 kg |
Input Power Supply Voltage | 100 to 240 V AC (85 to 264 V AC) | ||
---|---|---|---|
Input Frequency | 50/60 Hz ±5% | ||
Input Voltage Strain Factor | Within 5% | ||
Input Maximum Apparent Power | 160 VA | ||
Inrush Current | 20 A within 8 ms | ||
Rated Output Current | 5 V DC | 9 A | |
Excess Current Protection | 5 V DC | 10.0 A or more | |
Excess Voltage Protection | 5 V DC | 5.5 to 6.5 V | |
Efficiency | 76% or more | ||
Allowable Momentary Power Loss Duration | Within 20 ms | ||
Withstand Voltage | 2,300 Vrms AC / 1 minute (altitude 0 to 2,000 m) between all inputs / LG at once and all outputs / FG at once | ||
Insulation Resistance | Between all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter | ||
Fuse | Built-in (cannot be replaced by the user) | ||
Contact Output Part | Applications | ERR Contact | |
Rated Switching Voltage/Current | 24 V DC, 0.5 A | ||
Minimum Switching Load | 5 V DC 1 mA | ||
Response Time | OFF→ON | 10 ms or less | |
ON→OFF | 12 ms or less | ||
Lifespan | Mechanical | 20,000,000 operations or more | |
Electrical | Rated switching voltage/current 100,000 times or more | ||
Surge Protector | No | ||
Fuse | No | ||
External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) | |
Width (W) | 54.6 mm | ||
Depth (D) | 110 mm | ||
Mass | 0.46 kg |
R63RP external appearance
R63RP dimensional outline drawing
(Unit: mm)
Input Power Supply Voltage | 24 V DC (19.2 to 31.2 V DC) | ||
---|---|---|---|
Input Maximum Power | 50 W | ||
Inrush Current | 100 A within 1 ms | ||
Rated Output Current | 5 V DC | 6.5 A | |
Excess Current Protection | 5 V DC | 7.1 A or more | |
Excess Voltage Protection | 5 V DC | 5.5 to 6.5 V | |
Efficiency | 70% or more | ||
Allowable Momentary Power Loss Duration | Within 10 ms | ||
Withstand Voltage | 50 V AC / 1 minute (altitude 0 to 2,000 m) Between primary side and 5 V DC | ||
Insulation Resistance | Between all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter | ||
Fuse | Built-in (cannot be replaced by the user) | ||
Contact Output Part | Applications | ERR Contact | |
Rated Switching Voltage/Current | 24 V DC, 0.5 A | ||
Minimum Switching Load | 5 V DC 1 mA | ||
Response Time | OFF→ON | 10 ms or less | |
ON→OFF | 12 ms or less | ||
Lifespan | Mechanical | 20,000,000 operations or more | |
Electrical | Rated switching voltage/current 100,000 times or more | ||
Surge Protector | No | ||
Fuse | No | ||
External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) | |
Width (W) | 54.6 mm | ||
Depth (D) | 110 mm | ||
Mass | 0.41 kg |
R64RP external appearance
R64RP dimensional outline drawing
(Unit: mm)
Input Power Supply Voltage | 100 to 240 V AC (85 to 264 V AC) | ||
---|---|---|---|
Input Frequency | 50/60 Hz ±5% | ||
Input Voltage Strain Factor | Within 5% | ||
Input Maximum Apparent Power | 160 VA | ||
Inrush Current | 20 A within 8 ms | ||
Rated Output Current | 5 V DC | 9 A | |
Excess Current Protection | 5 V DC | 10.0 A or more | |
Excess Voltage Protection | 5 V DC | 5.5 to 6.5 V | |
Efficiency | 76% or more | ||
Allowable Momentary Power Loss Duration | Within 20 ms | ||
Withstand Voltage | 2,300 Vrms AC / 1 minute (altitude 0 to 2,000 m) between all inputs / LG at once and all outputs / FG at once | ||
Insulation Resistance | Between all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter | ||
Fuse | Built-in (cannot be replaced by the user) | ||
Contact Output Part | Applications | ERR Contact | |
Rated Switching Voltage/Current | 24 V DC, 0.5 A | ||
Minimum Switching Load | 5 V DC 1 mA | ||
Response Time | OFF→ON | 10 ms or less | |
ON→OFF | 12 ms or less | ||
Lifespan | Mechanical | 20,000,000 operations or more | |
Electrical | Rated switching voltage/current 100,000 times or more | ||
Surge Protector | No | ||
Fuse | No | ||
External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) | |
Width (W) | 54.6 mm | ||
Depth (D) | 110 mm | ||
Mass | 0.46 kg |
Part Number |
---|
R61P |
R62P |
R63P |
R63RP |
R64P |
R64RP |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to ShipSố ngày giao hàng |
---|---|---|---|---|
2,227,500 VND | 1 Piece(s) | Quote | ||
2,595,000 VND | 1 Piece(s) | Quote | ||
3,902,500 VND | 1 Piece(s) | Quote | ||
9,475,000 VND | 1 Piece(s) | Quote | ||
3,947,500 VND | 1 Piece(s) | Quote | ||
11,143,750 VND | 1 Piece(s) | Quote |
Loading...Tải…
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy