iQ-R Series Power Supply Unit

:
MITSUBISHI

    iQ-R Series Power Supply Unit
    The MELSEC iQ-R Series Power Supply Units are designed to provide reliable and efficient power solutions for automation systems
    [Feature]
    • Versatile Input Options: Supports both AC and DC input configurations.
    • For instance, the R63P is an DC power supply unit, while the R64P designed for AC power supply, ensuring compatibility with various electrical systems
    • Compact Design: These power supply units are designed for easy installation in compact spaces
    [Application]
    The Power Supply Units are ideal for a wide range of industrial automation application

    iQ-R Series Power Supply Unit Specifications

    R61P external appearance

    R61P external appearance

    R61P dimensional outline drawing

    R61P dimensional outline drawing

     

    (Unit: mm)

     

    Input Power Supply Voltage100 to 240 V AC (85 to 264 V AC)
    Input Frequency50/60 Hz ±5%
    Input Voltage Strain FactorWithin 5%
    Input Maximum Apparent Power130 VA
    Inrush Current20 A within 8 ms
    Rated Output Current5 V DC6.5 A
    Excess Current Protection5 V DC7.1 A or more
    Excess Voltage Protection5 V DC5.5 to 6.5 V
    Efficiency76% or more
    Allowable Momentary Power Loss DurationWithin 20 ms
    Withstand Voltage2,300 Vrms AC / 1 minute (altitude 0 to 2,000 m)
    between all inputs / LG at once and all outputs / FG at once
    Insulation ResistanceBetween all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter
    FuseBuilt-in (cannot be replaced by the user)
    Contact Output PartApplicationsERR Contact
    Rated Switching Voltage/Current24 V DC, 0.5 A
    Minimum Switching Load5 V DC 1 mA
    Response TimeOFF→ON10 ms or less
    ON→OFF12 ms or less
    LifespanMechanical20,000,000 operations or more
    ElectricalRated switching voltage/current 100,000 times or more
    Surge ProtectorNo
    FuseNo
    External DimensionsHeight (H)106 mm (98 mm at the base unit mounting part)
    Width (W)54.6 mm
    Depth (D)110 mm
    Mass0.41 kg

     

    (Unit: mm)

     

    R62P/R63P/R64P dimensional outline drawing

    R62P/R63P/R64P dimensional outline drawing

    R62P Specifications

    Input Power Supply Voltage100 to 240 V AC (85 to 264 V AC)
    Input Frequency50/60 Hz ±5%
    Input Voltage Strain FactorWithin 5%
    Input Maximum Apparent Power120 VA
    Inrush Current20 A within 8 ms
    Rated Output Current5 V DC3.5 A
    24 V DC0.6 A
    Excess Current Protection5 V DC3.8 A or more
    24 V DC0.66 A or more
    Excess Voltage Protection5 V DC5.5 to 6.5 V
    Efficiency76% or more
    Allowable Momentary Power Loss DurationWithin 20 ms
    Withstand Voltage2,300 Vrms AC / 1 minute (altitude 0 to 2,000 m)
    between all inputs / LG at once and all outputs / FG at once
    Insulation ResistanceBetween all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter
    FuseBuilt-in (cannot be replaced by the user)
    Contact Output PartApplicationsERR Contact
    Rated Switching Voltage/Current24 V DC, 0.5 A
    Minimum Switching Load5 V DC 1 mA
    Response TimeOFF→ON10 ms or less
    ON→OFF12 ms or less
    LifespanMechanical20,000,000 operations or more
    ElectricalRated switching voltage/current 100,000 times or more
    Surge ProtectorNo
    FuseNo
    External DimensionsHeight (H)106 mm (98 mm at the base unit mounting part)
    Width (W)54.6 mm
    Depth (D)110 mm
    Mass0.45 kg

    R63P Specifications

    Input Power Supply Voltage24 V DC (15.6 to 31.2 V DC)
    Input Maximum Power50 W
    Inrush Current100 A within 1 ms
    Rated Output Current5 V DC6.5 A
    Excess Current Protection5 V DC7.1 A or more
    Excess Voltage Protection5 V DC5.5 to 6.5 V
    Efficiency70% or more
    Allowable Momentary Power Loss DurationWithin 10 ms
    Withstand Voltage50 V AC / 1 minute (altitude 0 to 2,000 m)
    Between primary side and 5 V DC
    Insulation ResistanceBetween all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter
    FuseBuilt-in (cannot be replaced by the user)
    Contact Output PartApplicationsERR Contact
    Rated Switching Voltage/Current24 V DC, 0.5 A
    Minimum Switching Load5 V DC 1 mA
    Response TimeOFF→ON10 ms or less
    ON→OFF12 ms or less
    LifespanMechanical20,000,000 operations or more
    ElectricalRated switching voltage/current 100,000 times or more
    Surge ProtectorNo
    FuseNo
    External DimensionsHeight (H)106 mm (98 mm at the base unit mounting part)
    Width (W)54.6 mm
    Depth (D)110 mm
    Mass0.41 kg

    R64P Specifications

    Input Power Supply Voltage100 to 240 V AC (85 to 264 V AC)
    Input Frequency50/60 Hz ±5%
    Input Voltage Strain FactorWithin 5%
    Input Maximum Apparent Power160 VA
    Inrush Current20 A within 8 ms
    Rated Output Current5 V DC9 A
    Excess Current Protection5 V DC10.0 A or more
    Excess Voltage Protection5 V DC5.5 to 6.5 V
    Efficiency76% or more
    Allowable Momentary Power Loss DurationWithin 20 ms
    Withstand Voltage2,300 Vrms AC / 1 minute (altitude 0 to 2,000 m)
    between all inputs / LG at once and all outputs / FG at once
    Insulation ResistanceBetween all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter
    FuseBuilt-in (cannot be replaced by the user)
    Contact Output PartApplicationsERR Contact
    Rated Switching Voltage/Current24 V DC, 0.5 A
    Minimum Switching Load5 V DC 1 mA
    Response TimeOFF→ON10 ms or less
    ON→OFF12 ms or less
    LifespanMechanical20,000,000 operations or more
    ElectricalRated switching voltage/current 100,000 times or more
    Surge ProtectorNo
    FuseNo
    External DimensionsHeight (H)106 mm (98 mm at the base unit mounting part)
    Width (W)54.6 mm
    Depth (D)110 mm
    Mass0.46 kg

    R63RP Specifications

    R63RP external appearance

    R63RP external appearance

    R63RP dimensional outline drawing

    R63RP dimensional outline drawing

     

    (Unit: mm)

     

    Input Power Supply Voltage24 V DC (19.2 to 31.2 V DC)
    Input Maximum Power50 W
    Inrush Current100 A within 1 ms
    Rated Output Current5 V DC6.5 A
    Excess Current Protection5 V DC7.1 A or more
    Excess Voltage Protection5 V DC5.5 to 6.5 V
    Efficiency70% or more
    Allowable Momentary Power Loss DurationWithin 10 ms
    Withstand Voltage50 V AC / 1 minute (altitude 0 to 2,000 m)
    Between primary side and 5 V DC
    Insulation ResistanceBetween all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter
    FuseBuilt-in (cannot be replaced by the user)
    Contact Output PartApplicationsERR Contact
    Rated Switching Voltage/Current24 V DC, 0.5 A
    Minimum Switching Load5 V DC 1 mA
    Response TimeOFF→ON10 ms or less
    ON→OFF12 ms or less
    LifespanMechanical20,000,000 operations or more
    ElectricalRated switching voltage/current 100,000 times or more
    Surge ProtectorNo
    FuseNo
    External DimensionsHeight (H)106 mm (98 mm at the base unit mounting part)
    Width (W)54.6 mm
    Depth (D)110 mm
    Mass0.41 kg

    R64RP Specifications

    R64RP external appearance

    R64RP external appearance

    R64RP dimensional outline drawing

    R64RP dimensional outline drawing

     

    (Unit: mm)

     

    Input Power Supply Voltage100 to 240 V AC (85 to 264 V AC)
    Input Frequency50/60 Hz ±5%
    Input Voltage Strain FactorWithin 5%
    Input Maximum Apparent Power160 VA
    Inrush Current20 A within 8 ms
    Rated Output Current5 V DC9 A
    Excess Current Protection5 V DC10.0 A or more
    Excess Voltage Protection5 V DC5.5 to 6.5 V
    Efficiency76% or more
    Allowable Momentary Power Loss DurationWithin 20 ms
    Withstand Voltage2,300 Vrms AC / 1 minute (altitude 0 to 2,000 m)
    between all inputs / LG at once and all outputs / FG at once
    Insulation ResistanceBetween all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance meter
    FuseBuilt-in (cannot be replaced by the user)
    Contact Output PartApplicationsERR Contact
    Rated Switching Voltage/Current24 V DC, 0.5 A
    Minimum Switching Load5 V DC 1 mA
    Response TimeOFF→ON10 ms or less
    ON→OFF12 ms or less
    LifespanMechanical20,000,000 operations or more
    ElectricalRated switching voltage/current 100,000 times or more
    Surge ProtectorNo
    FuseNo
    External DimensionsHeight (H)106 mm (98 mm at the base unit mounting part)
    Width (W)54.6 mm
    Depth (D)110 mm
    Mass0.46 kg
    R63P | iQ-R Series Power Supply Unit | MITSUBISHI | MISUMI Vietnam