(!) Since support from Microsoft will end on January 14th, 2020, Windows 7 will be excluded from the recommended environment from December 15th, 2019 on this site. Vì lý do Microsoft kết thúc hỗ trợ cho Windows 7 vào ngày 14/01/2020, Windows 7 sẽ là hệ điều hành không được khuyến khích sử dụng với trang web này từ ngày 15/12/2019.
Select part number to Order Now/ Add to Cart
[Features]
· Weekly control using a large clock display.
· A daily time switch of a setting type that can be set while in dialog with both sides, and with a large display with a clock.
· Simple to operate with five keys.
· ON/OFF time schedule setting has 24 steps.
· AC100 to 230V free power source.
· Has a warranty for long duration power outage (approx. 10 years).
· International safety standard UL, CSA acquired.
· Day-to-day operations are possible with the same settings as timer operation.
H5L-A external appearance
H5L-A dimensional drawing
Units: mm
Note: Values in parentheses are the dimensions when the Y92A-96A front cover (sold separately) is installed.
Dimensional drawing when embedded
Panel cut size (DIN 43700 compliant)
Units: mm
Note: Mounting panel plate thickness is 1 to 3.2 mm.
Dimensional drawing when surface mounted
Mounting hole processing dimensional drawing
Units: mm
Dimensional drawing when DIN rail mounted
Units: mm
*1 For PFP-100N, PFP-50N.
* 2 for Series PFP-100N2.
Wiring Method | Screw-Fastening Terminal |
---|---|
Control Output | 2 Circuit (1a × 2) |
Single Cycle Time | 24 h × 7 days (work day can be specified)* |
Minimum Setting Unit | 1 min units |
Number Of Program Steps (2 Circuits Total) | 24 (1 step for ON or OFF) |
Format | Series H5L-A |
*The decision to run the program can be set daily for each day of the week.
Power Supply Voltage | 100 to 240 V AC, 50/60 Hz (Common) |
---|---|
Allowable Voltage Variation Range | 85 to 110% of power supply voltage |
Power Consumption | Approx. 4 VA (When 240 V AC) |
Control Output* | 250 V AC, 15 A resistant load (ambient temperature 50°C) 250 V AC, 12 A (Japanese Act on Product Safety of Electrical Appliances and Materials certified rating) resistive load (ambient temperature 55°C) |
Power Failure Compensation Method | Lithium Battery System |
Ambient Operating Temperature | -10 to +55℃ (No Freezing) |
Ambient Operating Humidity | 35 to 85% |
Case Exterior | Light Gray (Munsell 5Y7/1) |
*Minimum applied load 5 V DC, 100 mA (P level, reference value)
Variations In Operating Time | (±0.01% ±0.05 s) or less *1 | ||
---|---|---|---|
Set Error | |||
Voltage Effect | |||
Temperature Effect | |||
Time Accuracy | ±15 s/month (at 25°C) | ||
Compensation Time For Power Outage | Continuous 10 years or more (25°C) *2 | ||
Insulation Resistance | 100 MΩ or more | ||
Test Points | I Between conductive part terminal and exposed non-charging metal part | ||
II Between operation power supply circuit and contact control output circuit | |||
III Between discontinuous contacts | |||
Withstand Voltage | 2,000 V AC, 50/60 Hz, 1 min (test points are insulation resistance test points I, II) 1,000 V AC, 50/60 Hz, 1 min (test point is insulation resistance test point III) | ||
Impulse Voltage | 3 kV between operation power supply terminals 4.5 kV between conductive part terminal and exposed non-charging metal part | ||
Noise Resistance | Square-wave noise by noise simulator 2 kV (width 100 ns, rise 1 ns, polarity ±, phase 0 to 360°) | ||
Electrostatic Strength | 8 kV (Malfunction) | ||
Vibration | Endurance | 10 to 55 Hz, half amplitude 0.375mm, 3 directions, 2 h each | |
Malfunction | 10 to 55 Hz, half amplitude 0.25mm, 3 directions, 10 min each | ||
Shock | Endurance | 300 m/s2, 6 directions, 3 times each | |
Malfunction | 100m/s2, 6 directions, 4 times each | ||
Life | 100,000 operations or more (resistive load, 250 V AC, 15 A) | ||
Mass | Approx. 350g |
*1. Total error including variations in operating time, set errors, and the effects of voltage and temperature are within (±0.01% ±0.05 s). Additionally, ±0.01% is the value for the set time interval.
*2. Display and output are not available when the power supply is OFF.
Part Number |
---|
H5L-A |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to ShipSố ngày giao hàng |
---|---|---|---|---|
4,500,000 VND | 1 Piece(s) | 11 Day(s) |
Loading...Tải…
Type | Timer | Display method | Liquid Crystal | Mounting Method | Panel / surface mount (shared) |
---|---|---|---|---|---|
Time specifications(s) | 1 min – 23 h 59 min × 7 days | Power Supply Voltage | AC/DC | Output Method | Relay |
Dimension vertical(mm) | 96 | Dimension width(mm) | 96 | Dimension depth(mm) | 56.5 |
Rated power supply voltage(V) | AC 100–240 | Contact Configuration | 1a×2 |
Please check the type/dimensions/specifications of the part H5L-A in the Daily time switch H5L series.Vui lòng kiểm tra kiểu/kích thước/thông số kỹ thuật của phần H5L-A trong chuỗi Daily time switch H5L.
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy