(!) Since support from Microsoft will end on January 14th, 2020, Windows 7 will be excluded from the recommended environment from December 15th, 2019 on this site. Vì lý do Microsoft kết thúc hỗ trợ cho Windows 7 vào ngày 14/01/2020, Windows 7 sẽ là hệ điều hành không được khuyến khích sử dụng với trang web này từ ngày 15/12/2019.
Select part number to Order Now/ Add to Cart
Miniaturized control panel (UL/cUR product)
NF30-FAU
NF50-FAU
NF50-FHU
Type | No-Fuse Breaker | ||||||||
---|---|---|---|---|---|---|---|---|---|
Frame A | 30 | 50 | 50 | ||||||
Type Name | NF30-FAU | NF50-FAU | NF50-FHU | ||||||
Phase Wire System (Note 1) | - | - | - | ||||||
Number Of Contacts | 2 | 3 | 2 | 3 | 2 | 3 | |||
Rated Current A (Standard Ambient Temperature 40°C) | 5 10 15 20 30 | 5 10 15 20 30 40 50 | 3 5 10 15 20 30 40 50 | ||||||
Rated Current For Motor Protection (Note 8) | 2 4 6.3 8 16 | 0.3 0.4 0.6 0.8 1.2 1.4 2 2.5 4 7.1 8 12 16 25 32 45 | |||||||
Electrical Leakage Properties | High Speed Type | Rate Sensitivity Current I △n mA | - | - | - | ||||
Pickup Current UL1053 | - | - | - | ||||||
Maximum Operating Time s Or Less At 5I Δn (Note 2) | - | - | - | ||||||
Electrical Leakage Display Method | - | - | - | ||||||
Rated Short Circuit Breaking Capacity kA | UL 1077 CSA C22.2 No. 235 | Rated Voltage | AC (V) | 240 | 240 | 240 | |||
DC (V) | 60 | 60 | - | ||||||
AC | 240 V | 2.5 (Note 3) | 2.5 (Note 3) | 5 | |||||
DC | 60 V | 1.5 | 1.5 | - | |||||
IEC 60947-2 EN 60947-2 (Icu/Ics) | Rated Insulation Voltage (V) | 250 | 250 | 500 | |||||
AC | 400 V | - | - | 1.5/1 | |||||
230 V | 2.5/1 (Note 4) | 2.5/1 (Note 4) | 5/2 | ||||||
DC | 60 V | 1.5/1 | 1.5/1 | - | |||||
GB 14048.2 (Icu/Ics) | Rated Insulation Voltage (V) | 250 | 250 | 500 | |||||
AC | 415 V | - | - | 1.5/1 | |||||
240 V | - | - | 5/2 | ||||||
230 V | 2.5/1 (Note 4) | 2.5/1 (Note 4) | - | ||||||
DC | 60 V | 1.5/1 | 1.5/1 | - | |||||
JIS C 8201-2-1 Ann.1 Ann.2 (Icu/Ics) | Rated Insulation Voltage (V) | 250 | 250 | 500 | |||||
AC | 415 V | - | - | 1.5/1 | |||||
200 V | 2.5/1 (Note 4) | 2.5/1 (Note 4) | 5/2 | ||||||
DC | 65 V | 1.5/1 | 1.5/1 | - | |||||
JIS C 8201-2-2 Ann.1 Ann.2 (Icu/Ics) | Rated Operating Voltage AC (V) | - | - | - | |||||
AC | 200 V | - | - | - | |||||
100 V | - | - | - | ||||||
Rated Impulse Withstand Voltage Uimp (kV) | 2.5 | 2.5 | 4 | ||||||
Current Type | AC/DC shared | AC/DC shared | AC | ||||||
Isolation Compliant | - | - | - | ||||||
Reverse Connections | - | - | - | ||||||
External Dimensions (mm) | a | 40 | 60 | 40 | 60 | 50 | 75 | ||
b | 72 | 72 | 96 | ||||||
c | 57 | 57 | 60 | ||||||
ca | 73.5 | 73.5 | 76 | ||||||
Product Mass kg | 0.14 | 0.2 | 0.16 | 0.22 | 0.25 | 0.37 | |||
Mounting Method | IEC 35 mm Rail | ◎(Standard support for mounting IEC 35 mm rail) | ◎(Standard support for mounting IEC 35 mm rail) | ◎(Standard support for mounting IEC 35 mm rail) | |||||
Mounting Screw (Note 5) | Possible | Possible | Possible | ||||||
Front Plate Installation (Note 6) | Possible | Possible | - | ||||||
Electrical Appliance And Material Safety Law | compliant | Compliant | Compliant | ||||||
CE Mark | TÜV certification | TÜV certification | TÜV certification | ||||||
CCC Certification | acquired | acquired | acquired | ||||||
Overcurrent Tripping Method | Thermal | Thermal | Completely electromagnetic | ||||||
Trip Button | -(Note 7) | -(Note 7) | -(Note 7) |
Note 1: When using a 3-contact earth leakage breaker for 1 ø 2 W, do not use the center contact. Connect the left and right contacts.
When using for 1 ø 3 W, connect the center contact to a neutral wire. (UL cannot use 1 ø 3 W.)
Note 2: 0.1 for UL1053.
Note 3: The rated breaking capacity is 1.5 kA for parts with 5 A rated current.
Note 4: The rated breaking capacity is 1.5/1 kA for parts with 5 A rated current.
Note 5: The customer must provide the mounting screws. For details, please refer to the catalog.
Note 6: Can install surface plate without tightening nuts from the back. (The customer must provide the mounting screws M5 × 0.8 × 30) Here, terminal screws can be tightened from the back of the breaker.
Note 7: Only included when an alarm switch (AL) is attached. (Excludes NF30-FAU and NF50-FAU SHT+AL)
Note 8: For rated current for motor protection, only current sensitivities of 30 mA or 50 mA can be manufactured.
Rated Voltage | Applicable Circuit Voltage | Variable Voltage Range In Which Electrical Leakage Protection Function Can Operate |
---|---|---|
100-200 V | 100/110/200/220 V | 80 to 242 V |
240 V (UL) | 240 V | 132 to 264 V |
240 V (GB) | 240 V | 204 to 264 V |
230 V | 240 V | 195 to 253 V |
Part Number |
---|
NF30-FAU 2P 5A |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to ShipSố ngày giao hàng | Number of Poles | Rated Current (A) | Dimension width (mm) | Rated block capacity AC 240 V (kA) |
---|---|---|---|---|---|---|---|---|
741,250 VND | 1 Piece(s) | Quote | 2 | 5 | 40 | 1.5 |
Loading...Tải…
Ampere frame | 30AF | Rated block capacity, voltages except VAC 100/200/400, VDC 250 | Available | Mounting Method | DIN/Screw retention |
---|---|---|---|---|---|
Connection Method | Surface type | Representative Standard | PSE / CE / UL / TUV / CCC | Dimension height(mm) | 72 |
Dimension depth(mm) | 73.5 | Type | No fuse breaker (standard product) | Motor breaker(Apply) | Not applicable |
Please check the type/dimensions/specifications of the part NF30-FAU 2P 5A in the Molded Case Circuit Breakers (MCCB) NF-FAU Series series.Vui lòng kiểm tra kiểu/kích thước/thông số kỹ thuật của phần NF30-FAU 2P 5A trong chuỗi Molded Case Circuit Breakers (MCCB) NF-FAU Series.
Part Number |
---|
NF30-FAU 2P 20A |
NF30-FAU 3P 30A |
Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to ShipSố ngày giao hàng | Number of Poles | Rated Current (A) | Dimension width (mm) | Rated block capacity AC 240 V (kA) |
---|---|---|---|---|---|---|---|---|
741,250 VND | 1 Piece(s) | Quote | 2 | 20 | 40 | 2.5 | ||
887,500 VND | 1 Piece(s) | Quote | 3 | 30 | 60 | 2.5 |
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy