(!) Since support from Microsoft will end on January 14th, 2020, Windows 7 will be excluded from the recommended environment from December 15th, 2019 on this site. Vì lý do Microsoft kết thúc hỗ trợ cho Windows 7 vào ngày 14/01/2020, Windows 7 sẽ là hệ điều hành không được khuyến khích sử dụng với trang web này từ ngày 15/12/2019.
Select part number to Order Now/ Add to Cart
Direct drive capable transistor output (DC24V0.1A) can be operated directly.
Prepared easily removable terminal cover, separated for the main body and the unit, as standard equipment. Finger protection function prevents electric shock and improves safety during maintenance and inspection. The screw tightening holes provided in the terminal cover serve as screwdriver guides, decreasing screw tightening failures.
Using twin auxiliary contacts enables accommodating up to a low level of 5 V DC 3 mA (failure rate is 5 × 10-7/time in a normal environment where no dust or corrosive gas exists.).
Safety opening function (auxiliary b contact off when welding main contact). Meets requirements of EN regulations EN60204-1 “electrical equipment in industrial machines,” “control functions during fault.” Can use as interlock circuit contact.
Rail mounting is standard. Can mount as standard product onto 35 mm rail compliant to IEC and DIN regulations.
Thermal relay can be mounted without adapter. Can install directly to contactor, and therefore can easily change to electromagnetic switch, simply by additional purchase of a thermal relay.
Displays IEC compatible terminal number on front of product main body. To easily distinguish a and b contacts, the identification codes (NO, NC) are displayed on the front of the product main body.
Contributes to small control panel. Can use for 440 V AC circuit, despite the small size.
Type Name | SD-Q11 | SD-Q12 | |
---|---|---|---|
External Dimensions | Height | 65% | 67% |
Depth | 60% | 61% | |
Mounting Surface Area | 68% | 70% |
Type Name | Type | Non-Reversible | |||
---|---|---|---|---|---|
Electromagnetic Contactor SD- | Q11 | Q12 | |||
Rated Insulation Voltage [V] | 690 | ||||
Rated Operating Current [A] | Three-Phase Squirrel-Cage Motor (AC-3 Class) | 200 To 240 V | 12 | ||
380 To 440 V | 9 | ||||
500 To 550 V | 7 | ||||
Single-Phase Motor (AC-3 Class) | 100 To 110 V | 8 | |||
200 To 220 V | 6 | ||||
Resistance Load (AC-1 Class) | 100 To 220 V | 10 (15) Note 1 | |||
380 To 440 V | 10 | ||||
DC Motor * (DC2, DC4 Class) | 2-Contact In-Line | 24 V | 12 | ||
48 V | 6 | ||||
100 To 110 V | 1.2 | ||||
3-Contact In-Line | 24 V | 12 | |||
48 V | 10 | ||||
100 To 110 V | 2.5 | ||||
Rated Capacity [kW] | Three-Phase Squirrel-Cage Motor (AC-3 Class) | 200 To 240 V | 2.5 | ||
380 To 440 V | 4 | ||||
500 To 550 V | 4 | ||||
Single-Phase Motor (AC-3 Class) | 100 To 110 V | 0.2 | |||
200 To 220 V | 0.4 | ||||
Open Thermal Current [A] | 20 | ||||
Breaking Current Capacity [A] | 220 V | 120 | |||
440 V | 90 | ||||
Closing Current Capacity [A] | 220 V | 120 | |||
440 V | 90 | ||||
Switching Frequency [Times/Hour] | 1,800 | ||||
Switching Durability [10,000 Times] | Electrical (AC-3 Class) | 100 | |||
Mechanical | 1,000 |
Note 1: The electrical durability is when operating at a ripple rate less than the three-phase full-wave rectification. 800,000 times for single-phase full-wave rectification. Also, the electrical durability for those other than three-phase squirrel-cage motor (AC-3 class) is 500,000 times (however, the rating in ( ) for resistance loads from 200 to 220 V is 250,000 times).
Note 2: Compliance and conforming standards: JIS C8201-4-1, IEC 60947-4-1(* DC2 and DC4 classes are JEM 1038 only).
Part Number |
---|
SD-Q11 DC24V 1A |
SD-Q11 DC24V 1B |
SD-Q12 DC24V 1A1B |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to ShipSố ngày giao hàng | Auxiliary Contact | Dimension width (mm) |
---|---|---|---|---|---|---|
1,105,000 VND | 1 Piece(s) | Quote | 1a | 45 | ||
1,105,000 VND | 1 Piece(s) | Quote | 1b | 45 | ||
1,490,000 VND | 1 Piece(s) | Quote | 1a1b | 54.5 |
Loading...Tải…
Operating Method | Irreversible type | Coil rated voltage(V) | DC24 | Number of Poles | 3 |
---|---|---|---|---|---|
Representative Standard | CE / UL / TUV / CCC / CSA | Dimension length(mm) | 51 | Dimension thickness(mm) | 66.5 |
Equipment Name | Highly Sensitive Contactor | Rated current used resistance load (AC-1) AC 100 to 220 V(A) | 10 | Rated current used resistance load (AC-1) AC 380 to 440V(A) | 10 |
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy