(!) Since support from Microsoft will end on January 14th, 2020, Windows 7 will be excluded from the recommended environment from December 15th, 2019 on this site. Vì lý do Microsoft kết thúc hỗ trợ cho Windows 7 vào ngày 14/01/2020, Windows 7 sẽ là hệ điều hành không được khuyến khích sử dụng với trang web này từ ngày 15/12/2019.
Select part number to Order Now/ Add to Cart
[Features]
· The smallest type, available at low cost
· Proportional (P) motion is available in the adjustment mode. In addition, reset adjustment function has been added
· The mounting adapter enables continuous close-contact installation
· Plug-in method enables DIN rail mounting and panel embedding
Terminal arrangement
Power supply voltage | 100 to 240 V AC 50/60 Hz | |
---|---|---|
Allowable voltage fluctuation range | 90 to 110% of power supply voltage | |
Power Consumption | Approx. 3.6 VA | |
Input | Thermocouple (with burnout circuit) Platinum Resistance Thermometer Element compatible thermistor | |
Control method | ON/OFF operation, proportional operation (P) | |
Setting method | Analog setting | |
Indication system | No indications | |
Control Output | Relay output | 1c 250 V AC 3 A (resistant load) (However, the opening and closing capacity is 330 V A) |
Ambient operating temperature | -10 to +55℃ (however, no freezing or no condensation) | |
Operating ambient humidity | Relative humidity 45 to 85% |
*. Do not use the output of the inverter as a power supply.
Setting accuracy | ±2% FS or less (effect of electromagnetic interference ±4% FS or less) | |
---|---|---|
Adjustment sensitivity | 0.5% FS or less (fixed) | |
Proportional band | 3%FS (fixed) | |
Proportional period | Approx. 20 s | |
Reset range | 5±1%FS * 2 | |
Insulation Resistance | 20 MΩ or more (at 500 V DC megger) | |
Withstand Voltage | 2,000 V AC 50/60 Hz for 1 min (however, between the conductive terminal batch and the non-charged metal part) | |
Vibration | Malfunction | 10 to 55 Hz Single amplitude 0.15 mm X, Y, Z 10 min in each direction |
Durability | 16.7 Hz Single amplitude 2 mm X, Y, Z 2 h in each direction | |
Impact | Malfunction | 147 m/s^2, 6 directions, 3 times each |
Durability | 294 m/s^2, 6 directions, 3 times each | |
Life | Electrical | 100,000 times or more (110 V AC 3 A resistant load) |
Weight | Approx. 100 g (With recessed mounting adapter) | |
Protective Enclosure | IEC standard, front operation unit IP40, terminal unit IP00 | |
Applicable socket | Type P2CF-08 (sold separately), type P3G-08 (Sold separately) | |
Applicable front cover | Shape Y92A-48B (Sold separately) |
* 2. The ON/OFF operation type does not have a reset function.
The reset function is used to correct the offset during proportional operation.
If the offset occurs below the set value, turn the reset adjustment axis to the right (clockwise).
Part Number |
---|
E5C2-R20K AC100-240 0-200 |
E5C2-R20K AC100-240 0-300 |
E5C2-R20K AC100-240 0-400 |
E5C2-R20K AC100-240 0-600 |
E5C2-R40K AC100-240 0-300 |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to ShipSố ngày giao hàng | Input Method | Control Method | Number of Control Points | Standard scale (℃) |
---|---|---|---|---|---|---|---|---|
3,602,613 VND | 1 Piece(s) | 6 Day(s) or more | Thermocouple | ON/OFF Control | - | 0-200 | ||
3,072,861 VND | 1 Piece(s) | 6 Day(s) or more | Thermocouple | ON/OFF Control | - | 0-300 | ||
3,588,141 VND | 1 Piece(s) | 7 Day(s) or more | Thermocouple | ON/OFF Control | - | 0-400 | ||
3,588,141 VND | 1 Piece(s) | 7 Day(s) or more | Thermocouple | ON/OFF Control | - | 0-600 | ||
3,588,141 VND | 1 Piece(s) | 13 Day(s) or more | Thermocouple | P Control | - | 0-300 |
Loading...Tải…
Output Type | Relay contact | Number of Input Points(pcs.) | 1 | Failure Detecting Function | No |
---|---|---|---|---|---|
Power Supply Voltage(V) | 100 to 240 VAC | Control Output 1 | Relay |
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy