(!) Since support from Microsoft will end on January 14th, 2020, Windows 7 will be excluded from the recommended environment from December 15th, 2019 on this site. Vì lý do Microsoft kết thúc hỗ trợ cho Windows 7 vào ngày 14/01/2020, Windows 7 sẽ là hệ điều hành không được khuyến khích sử dụng với trang web này từ ngày 15/12/2019.
Select part number to Order Now/ Add to Cart
- CC-Link Safety Remote I/O modules, Terminal block type, MELSEC-QS Series from MITSUBISHI.
- 2 terminal block types available, Screw terminal block type and Spring clamp terminal block type.
- The system complying with Category 3 or Category 4 of EN 954-1 can be configured by the combination of wiring and parameters.
- Rated input voltage: 24 V DC
- Ingress protection level: IP2X
- The remote I/O module which has obtained the highest safety level applicable to programmable controllers, and the safety-related system with high security can be configured.
QS0J65BTB2-12DT-K image
Input Specifications | ||
---|---|---|
Number of Inputs | 8 (for duplexing input) 16 (for single output) | |
Rated Input Voltage | 24 V DC (ripple ratio within 5%) (allowable voltage range from 19.2 to 28.8 V DC) | |
Rated Input Current | Approx. 4.6 mA | |
Maximum Number of Simultaneous Input Points | 100% | |
ON Voltage / ON Current | 15 V DC or more / 2 mA or more | |
OFF Voltage / OFF Current | 5 V DC or less / 0.5 mA or less | |
Input Resistance | Approx. 5.6 kΩ | |
Input Format | DC input (negative common type) | |
Input Response Time | OFF > ON | 0.4 ms or less (24 V DC) |
ON > OFF | 0.4 ms or less (24 V DC) | |
Safety Remote Station Input Response Time | 11.2 ms or less + denoising filter time (1 ms, 5 ms, 10 ms, 20 ms, 50 ms) | |
Input Common Method | 16 points 1 common (terminal block model, 2-wire type) | |
Input Insulation Method | Opto-isolator insulation | |
Output Specifications | ||
Number of Outputs | 4 points (when selecting source + sink type) 2 points (when selecting source + source type) | |
Rated Load Voltage | 24 V DC | |
Operating Load Voltage Range | 19.2 to 28.8 V DC (Ripple ratio within 5%) | |
Maximum Load Current | 0.5 A / 1 point | |
Maximum Inrush Current | 1.0 A, 10 ms or less | |
Leakage Current When OFF | 0.5 mA or less | |
Maximum Voltage Drop When ON | 1.0 V DC or less | |
Protection Function | Output Overload Protection Function | |
Output Format | Source + sink type Source + source type | |
Output Response Time | OFF > ON | 0.4 ms or less (24 V DC) |
ON > OFF | 0.4 ms or less (24 V DC) | |
Safety Remote Station Output Response Time | OFF > ON | 11.2 ms or less |
ON > OFF | 10.4 ms or less | |
Surge Suppressor | Zener diode | |
Output Common Method | 4 points 1 common (terminal block model, 2-wire type) | |
Common Current | Maximum 4 A (total of input and output) | |
Output Insulation Method | Opto-isolator insulation | |
Common Specifications | ||
Dielectric Strength | Between all DC external terminals as a whole and the earth: 500 V AC for 1 minute | |
Insulation Resistance | Between all DC external terminals as a whole and the earth: 10 MΩ or more at 500 V DC on an ohmmeter | |
Protection Grade | IP2X | |
Station Type | Safety remote I/O station | |
Number of Occupied Stations | 1 | |
Number of Accesses to the Non-volatile Memory Inside the Unit | 1012 | |
Safety Remote Station Refresh Response Process Time | 9.6 ms | |
External Power Supply | Voltage | 19.2 to 28.8 V DC (Ripple ratio within 5%) |
Current | 60 mA (for 24 V DC and with all points ON, not including external load current) | |
Protection Function | External supply power overvoltage protection function, external supply power overcurrent protection function | |
Fuse | 8 A (non-replaceable) | |
Unit Power Supply | Voltage | 19.2 to 28.8 V DC (Ripple ratio within 5%) |
Current | 140 mA or less (24 V DC, with all points are ON) | |
Protection Function | Unit power supply overvoltage protection function, unit power supply overcurrent protection function | |
Fuse | 0.8 A (non-replaceable) | |
Allowable Momentary Power Loss Time | Within 10 ms | |
External Wiring Connection Method | Communication part, unit power supply part: 7-point 2-piece terminal block (M3 screw) Input/output power supply, input/output part: 18-point 2-piece terminal block (M3 screw) x 3 | |
Weight | 0.71 kg |
Ambient Operating Temperature | 0 to 55°C | ||
---|---|---|---|
Ambient Storage Temperature | -40 to 75°C | ||
Ambient Operating Humidity | 5 to 95% RH, assuming non-condensing | ||
Ambient Storage Humidity | 5 to 95% RH, assuming non-condensing | ||
Vibration Resistance | JIS B 3502, IEC 61131-2 Compatible | Under Intermittent Vibration | Frequency: 5 to 8.4 Hz, Single amplitude: 3.5 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 9.8 m/s2 Sweeps: 10 sweeps in each direction of X, Y and Z |
Under Continuous Vibration | Frequency: 5 to 8.4 Hz, Single amplitude: 1.75 mm Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m/s2 | ||
Impact Resistant | JIS B 3502, IEC 61131-2 compatible (147 m/s2,for a duration of 11 ms, 3 times in 3 directions of X, Y and Z with a half-sine pulse) | ||
Operating Atmosphere | No Corrosive Gas | ||
Operating Altitude | 0 to 2,000 m | ||
Installation Location | Inside the control panel | ||
Overvoltage Category | II or lower | ||
Pollution Degree | 2 or less | ||
Equipment Class | Class III |
Part Number |
---|
QS0J65BTB2-12DT |
QS0J65BTB2-12DT-K |
QS0J65BTS2-4T |
QS0J65BTS2-8D |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to ShipSố ngày giao hàng | Representative Standard | Terminal shape | Type of unit |
---|---|---|---|---|---|---|---|
22,435,000 VND | 1 Piece(s) | Quote | CE / UL | - | CC-Link Safety Safe Input/Output | ||
17,741,250 VND | 1 Piece(s) | Quote | CE / UL / CUL | 2-piece terminal block | CC-Link Safety input/output | ||
12,381,250 VND | 1 Piece(s) | Quote | CE / UL | - | CC-Link Safety Safe Output | ||
14,237,500 VND | 1 Piece(s) | Quote | CE / UL | - | CC-Link Safety Safe Input |
Loading...Tải…
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy