iQ-R Series communication unit

- This product belongs in RoHS Directive under Category 9 "Monitoring and control equipment" with exclusion from the usage restriction of phthalate esters until 21 July 2021.
iQ-R Series Communication Unit
iQ-R Series Communication Unit offers a wide variety of product type to choose from.
[Feature and Product types]
• Energy measuring model - RE81WH
• AnyWireASLINK master module - RJ51AW12AL
• BACnet module - model RJ71BAC96 Transmission rate (bps) 100M/10M
• EtherNet/IP network interface module : model RJ71EIP91
• CC-Link system master/local module : model RJ61BT11
[Application]
iQ-R Series Communication Unit are ideal for a wide range of industrial automation application
iQ-R Series Communication Unit Specifications
AnyWireASLINK Master Unit RJ51AW12AL Specifications

AnyWireASLINK Master Unit RJ51AW12AL external appearance

AnyWireASLINK Master Unit RJ51AW12AL dimensional outline drawing
(Unit: mm)
| Transmission Clock | 27.0 kHz | |
|---|---|---|
| Maximum Transmission Distance (Total Extension) | 200 m | |
| Number of connectable units | Maximum 128 units (Varies depending on the current consumption of each slave unit.) | |
| Transmission method | DC power supply superimposed total frame / cyclic method | |
| Connection form | Bus type (multi-drop method, T-branching method, tree-branching method) | |
| Transmission Protocol | Dedicated protocol (AnyWireASLINK) | |
| Error Control Method | Checksum, double verification method | |
| Number Of Connected I/O Points | Maximum 512 points (256 input points / 256 output points) | |
| AnyWireASLINK Transmission Wire | ·UL compatible general purpose 2-wire cable (VCTF, VCT 1.25 mm^2, 0.75 mm^2, rated temperature 70°C or higher) ·UL compatible general-purpose cable (1.25 mm^2, 0.75 mm^2, rated temperature 70°C or higher) ·Dedicated ribbon cable (1.25 mm^2, 0.75 mm^2, rated temperature 90°C) | |
| 24 V DC Power Line | ·UL compatible general purpose 2-wire cable (VCTF, VCT 0.75 to 2.0 mm^2, rated temperature 70°C or higher) ·UL compatible general-purpose cable (0.75 to 2.0 mm^2, rated temperature 70°C or higher) ·Dedicated ribbon cable (1.25 mm^2, 0.75 mm^2, rated temperature 90°C) | |
| External Power Supply | Voltage | 21.6 to 27.6 V DC (24 V DC, -10 to +15%) ripple voltage 0.5 V p-p or less Recommended voltage: 26.4 V (24 V DC, +10%) |
| External Wiring Connection Method | 7‑Piece spring clamp terminal block, push-in type | |
| Transmission Wire Supply Current | When using 1.25 mm^2 cable: MAX 2 A When using 0.75 mm^2 cable: MAX 1.2 A | |
| Number Of Occupied Inputs/Outputs | 32 points (I/O assignment: Intelligent 32 points) | |
| 5 V DC Internal Current Consumption | 0.20 A | |
| External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) |
| Width (W) | 27.8 mm | |
| Depth (D) | 124 mm | |
| Weight | 0.13 kg | |
CC-Link System Master / Local Unit RJ61BT11 Specifications

CC-Link System Master / Local Unit RJ61BT11 external appearance

CC-Link System Master / Local Unit RJ61BT11 dimensional outline drawing
(Unit: mm)
| Transmission Speed | 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps (Selectable) | ||
|---|---|---|---|
| Station Type | Master station (Version 1 master station or version 2 master station) Local station (Version 1 local station or version 2 local station) | ||
| Maximum Number Of Connected Devices | Master Station | 64 devices | |
| Number Of Occupied Stations | Local Station | 1 to 4 stations | |
| Maximum Link Points Per System | CC-Link Ver. 1 | Remote input/output (RX, RY): 2,048 points Remote register (RWw): 256 points Remote register (RWr): 256 points | |
| CC-Link Ver. 2 | Remote input/output (RX, RY): 8,192 points Remote register (RWw): 2,048 points Remote register (RWr): 2,048 points | ||
| Link Points Per Station | CC-Link Ver. 1 | Remote input/output (RX, RY): 32 points (30 points for local stations) Remote register (RWw): 4 points Remote register (RWr): 4 points | |
| CC-Link Ver. 2 | Expanded cyclic setting: 1 times setting | Remote input/output (RX, RY): 32 points (30 points for local stations) Remote register (RWw): 4 points Remote register (RWr): 4 points | |
| Expanded cyclic setting: 2 times setting | Remote input/output (RX, RY): 32 points (30 points for local stations) Remote register (RWw): 8 points Remote register (RWr): 8 points | ||
| Expanded cyclic setting: 4 times setting | Remote input/output (RX, RY): 64 points (62 points for local stations) Remote register (RWw): 16 points Remote register (RWr): 16 points | ||
| Expanded Cyclic Setting: × 8 Setting | Remote input/output (RX, RY): 128 points (126 points for local stations) Remote register (RWw): 32 points Remote register (RWr): 32 points | ||
| Communication Method | Broadcast polling method | ||
| Synchronization Method | Frame Synchronization Method | ||
| Encryption Method | NRZI (Non Return to Zero Inverted) sign | ||
| Transmission Path Type | Bus (RS-485) | ||
| Transmission Format | HDLC Compliant | ||
| Error Control Method | CRC (X16+X12+X5+1) | ||
| Communication Cable | CC-Link dedicated cable compatible with Ver. 1.10 | ||
| Maximum total cable length (Maximum transmission distance) | Ver. 1.10 | At 156 kbps | 1,200 m |
| At 635 kbps | 900 m | ||
| At 2.5 Mbps | 400 m | ||
| At 5 Mbps | 160 m | ||
| At 10 Mbps | 100 m | ||
| Number Of Occupied Inputs/Outputs | 32 points (I/O assignment: Intelligent 32 points) | ||
| 5 V DC Internal Current Consumption | 0.34 A | ||
| External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) | |
| Width (W) | 27.8 mm | ||
| Depth (D) | 131 mm | ||
| Weight | 0.16 kg | ||
BACnet Unit RJ71BAC96 Specifications

BACnet Unit RJ71BAC96 external appearance

BACnet Unit RJ71BAC96 dimensional outline drawing
(Unit: mm)
| Transmission Specification | Data Transmission Speed | 100/10 Mbps |
|---|---|---|
| Communication Mode | Full Duplex / Half Duplex | |
| Transmission Method | Base Band | |
| Maximum Segment Length | 100 m (Length between the hub and the node) | |
| IP Version | IPv6/IPv4 | |
| BACnet Specification | Number Of Registrable Input/Output Objects | 4,000 instances |
| Number Of Registrable CA Objects | 300 instances | |
| Number Of Registrable SC Objects | 100 instances | |
| Number Of Registrable TL Objects | 200 instances | |
| Number Of Registrable NC Objects | 50 instances | |
| Registrable Capacity In Read Access Block Area | Total 2,176 points | |
| Registrable Capacity In Write Access Block Area | Total 2,176 points | |
| Registrable Capacity In BACnet Monitor Access Block Area | 10,000 points in total | |
| Registrable Capacity In COV Link Access Block Area | 10,000 points in total | |
| Registrable Capacity In Event Link Access Block Area | 10,000 points in total | |
| Number Of Occupied Inputs/Outputs | 32 points (I/O assignment: Intelligent 32 points) | |
| 5 V DC Internal Current Consumption | 0.61 A | |
| External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) |
| Width (W) | 27.8 mm | |
| Depth (D) | 110 mm | |
| Weight | 0.19 kg | |
Serial Communication Unit RJ71C24 Specifications

Serial Communication Unit RJ71C24 external appearance

Serial Communication Unit RJ71C24 dimensional outline drawing
(Unit: mm)
| Interface | CH. 1 | RS-232 Compliant (D-Sub 9P) | |
|---|---|---|---|
| CH. 2 | RS-422/485 Compliant (2‑piece Terminal Block) | ||
| Communication Method | Circuit | Full-duplex communication / Half-duplex communication | |
| MELSEC Communication Protocol Communication | Half-duplex communication | ||
| Communication Protocol Communication | Full-duplex communication / Half-duplex communication | ||
| Nonprocedural Protocol Communication | Full-duplex communication / Half-duplex communication | ||
| Bi-Directional Protocol Communication | Full-duplex communication / Half-duplex communication | ||
| Synchronization Method | Asynchronous Method | ||
| Transmission Speed | 1,200, 2,400, 4,800, 9,600, 14,400, 19,200, 28,800, 38,400, 57,600, 115,200, 230,400 bps | ||
| Data Format | Start Bit | 1 | |
| Data Bit | 7/8 | ||
| Parity Bit | 1 (vertical parity) / None | ||
| Stop Bit | 1/2 | ||
| Access Cycle | MELSEC Communication Protocol Communication | One request is processed as part of the END processing of the CPU unit of the C24-installed station | |
| Communication Protocol Communication | Both send and receive requests are executed based on a dedicated command. | ||
| Nonprocedural Protocol Communication | Sending is performed for each transmission request Reception is always possible | ||
| Bi-Directional Protocol Communication | Sending is performed for each transmission request Reception is always possible | ||
| Error Detection | MELSEC Communication Protocol Communication | Parity Check | Applicable |
| Checksum | Applicable | ||
| Horizontal Parity | Not applicable | ||
| 16‑Bit CRC (MODBUS Specification) | Not applicable | ||
| Communication Protocol Communication | Parity Check | Applicable | |
| Checksum | Applicable | ||
| Horizontal Parity | Applicable | ||
| 16‑Bit CRC (MODBUS Specification) | Applicable | ||
| Nonprocedural Protocol Communication | Parity Check | Applicable | |
| Checksum | Applicable | ||
| Horizontal Parity | Applicable | ||
| 16‑Bit CRC (MODBUS Specification) | Not applicable | ||
| Bi-Directional Protocol Communication | Parity Check | Applicable | |
| Checksum | Applicable | ||
| Horizontal Parity | Not applicable | ||
| 16‑Bit CRC (MODBUS Specification) | Not applicable | ||
| Transmission Control | RS-232 | DTR/DSR Control | Applicable |
| RS/CS Control | Applicable | ||
| CD (DCD) Signal Control | Applicable | ||
| DC1/DC3 (Xon/Xoff) Control | Applicable | ||
| DC2 / DC4 Control | Applicable | ||
| RS-422/485 | DTR/DSR Control | Not applicable | |
| RS/CS Control | Not applicable | ||
| CD (DCD) Signal Control | Not applicable | ||
| DC1/DC3 (Xon/Xoff) Control | Applicable | ||
| DC2 / DC4 Control | Applicable | ||
| Line configuration of connections (Coupling device-side: CPU unit side) | RS-232 | 1: 1 | |
| RS-422/485 | 1: 1, 1: n, n: 1, m: n (The total of n and m + n is up to 32) | ||
| Line configuration of data communications (Coupling device-side: CPU unit side) | RS-232 | MELSEC Communication Protocol Communication | 1: 1 |
| Communication Protocol Communication | 1: 1 | ||
| Nonprocedural Protocol Communication | 1: 1 | ||
| Bi-Directional Protocol Communication | 1: 1 | ||
| RS-422/485 | MELSEC Communication Protocol Communication | 1: 1, 1: n, m: n (The total of n and m + n is up to 32) | |
| Communication Protocol Communication | 1: 1, n: 1 (n is up to 32) | ||
| Nonprocedural Protocol Communication | 1: 1, 1: n, n: 1 (n is up to 32) | ||
| Bi-Directional Protocol Communication | 1: 1 | ||
| Transmission distance | RS-232 | Maximum 15 m | |
| RS-422/485 | Maximum 1,200 m (The total extension distance) | ||
| Number Of Occupied Inputs/Outputs | 32 points (I/O assignment: Intelligent 32 points) | ||
| 5 V DC Internal Current Consumption | 0.31 A | ||
| External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) | |
| Width (W) | 27.8 mm | ||
| Depth (D) | 110 mm | ||
| Weight | 0.16 kg | ||
Specifications of serial communication unit RJ71C24-R2

External appearance of serial communication unit RJ71C24-R2

Drawing of serial communication unit RJ71C24-R2
(Unit: mm)
| Interface | CH. 1 | RS-232 Compliant (D-Sub 9P) | |
|---|---|---|---|
| CH. 2 | RS-232 Compliant (D-Sub 9P) | ||
| Communication Method | Circuit | Full-duplex communication / Half-duplex communication | |
| MELSEC Communication Protocol Communication | Half-duplex communication | ||
| Communication Protocol Communication | Full-duplex communication / Half-duplex communication | ||
| Nonprocedural Protocol Communication | Full-duplex communication / Half-duplex communication | ||
| Bi-Directional Protocol Communication | Full-duplex communication / Half-duplex communication | ||
| Synchronization Method | Asynchronous Method | ||
| Transmission Speed | 1,200, 2,400, 4,800, 9,600, 14,400, 19,200, 28,800, 38,400, 57,600, 115,200, 230,400 bps | ||
| Data Format | Start Bit | 1 | |
| Data Bit | 7/8 | ||
| Parity Bit | 1 (vertical parity) / None | ||
| Stop Bit | 1/2 | ||
| Access Cycle | MELSEC Communication Protocol Communication | One request is processed as part of the END processing of the CPU unit of the C24-installed station | |
| Communication Protocol Communication | Both send and receive requests are executed based on a dedicated command. | ||
| Nonprocedural Protocol Communication | Sending is performed for each transmission request Reception is always possible | ||
| Bi-Directional Protocol Communication | Sending is performed for each transmission request Reception is always possible | ||
| Error Detection | MELSEC Communication Protocol Communication | Parity Check | Applicable |
| Checksum | Applicable | ||
| Horizontal Parity | Not applicable | ||
| 16‑Bit CRC (MODBUS Specification) | Not applicable | ||
| Communication Protocol Communication | Parity Check | Applicable | |
| Checksum | Applicable | ||
| Horizontal Parity | Applicable | ||
| 16‑Bit CRC (MODBUS Specification) | Applicable | ||
| Nonprocedural Protocol Communication | Parity Check | Applicable | |
| Checksum | Applicable | ||
| Horizontal Parity | Applicable | ||
| 16‑Bit CRC (MODBUS Specification) | Not applicable | ||
| Bi-Directional Protocol Communication | Parity Check | Applicable | |
| Checksum | Applicable | ||
| Horizontal Parity | Not applicable | ||
| 16‑Bit CRC (MODBUS Specification) | Not applicable | ||
| Transmission Control | RS-232 | DTR/DSR Control | Applicable |
| RS/CS Control | Applicable | ||
| CD (DCD) Signal Control | Applicable | ||
| DC1/DC3 (Xon/Xoff) Control | Applicable | ||
| DC2 / DC4 Control | Applicable | ||
| Line configuration of connections (Coupling device-side: CPU unit side) | RS-232 | 1: 1 | |
| Line configuration of data communications (Coupling device-side: CPU unit side) | RS-232 | MELSEC Communication Protocol Communication | 1: 1 |
| Communication Protocol Communication | 1: 1 | ||
| Nonprocedural Protocol Communication | 1: 1 | ||
| Bi-Directional Protocol Communication | 1: 1 | ||
| Transmission distance | RS-232 | Maximum 15 m | |
| Number Of Occupied Inputs/Outputs | 32 points (I/O assignment: Intelligent 32 points) | ||
| 5 V DC Internal Current Consumption | 0.20 A | ||
| External Dimensions | Height (H) | 106 mm (98 mm at the base unit mounting part) | |
| Width (W) | 27.8 mm | ||
| Depth (D) | 110 mm | ||
| Weight | 0.14 kg | ||