Power Relay G7L

- The delivery date is unstable due to the difficulty in obtaining materials, components, etc. There is no prospect of the next arrival of products for which orders have been suspended.
A power relay with a high capacity and high dielectric strength that can handle momentary voltage drops.
[Features]
· No contact chattering for momentary voltage drops up to 50% of the rated voltage.
· A wide range coil that covers 100 V AC type from 100 to 120 V AC 50/60 Hz or 200 V AC type from 200 to 240 V AC 50/60 Hz with a single coil.
· High capacity that is particularly able to manage inductive loads with powerful force.
· All insulating materials are flame retardant and comply with UL94 V-0 standards.
· Comes in a wide variety of types including tab terminals, screw terminals, PCB terminals, etc. Surface connection sockets are also available.
· Standard products compliant with UL, CSA, and TÜV and meet the IEC950 standards.
· Safe design with 3 mm contact gap.
[Applications]
· Widely applicable to factory automation as well as non-factory automation equipment.
Power Relay Specifications of OMRON Industrial Relays

G7L external appearance of Industrial Relays

Model G7L-1A-T dimensional outline drawing (E-bracket mounting tab terminal type)

G7L-2A-T dimensional outline drawing (E-bracket mounting tab terminal type)

Mounting hole machining dimensions of Industrial Relays
Ratings Operation Coil of OMRON Industrial Relays
| Industrial Relays Item | Rated Current (mA) | Coil Resistance (Ω) | Coil Inductance (H) | Operating Voltage | Release Voltage | Maximum Permissible Voltage | Power Consumption (VA/W) | ||
|---|---|---|---|---|---|---|---|---|---|
| Rated Voltage (V) | Armature When ON | Armature When OFF | On the Basis of Rated Voltage | ||||||
| AC | 12 | 142 | - | - | - | 75% max. | 15% min. | 110% | Approx. 1.7 to 2.5 |
| 24 | 71 | ||||||||
| 50 | 34 | ||||||||
| 100 to 120 | 17.0 to 20.4 | 75 V max. | 18 V min. | 132 V | |||||
| 200 to 240 | 8.5 to 10.2 | 150 V max. | 36 V min. | 264 V | |||||
| DC | 6 | 317 | 18.9 | 0.09 | 0.21 | 75% max. | 15% min. | 110% | Approx. 1.9 |
| 12 | 158 | 75 | 0.37 | 0.88 | |||||
| 24 | 79 | 303 | 1.42 | 3.54 | |||||
| 48 | 40 | 1,220 | 6.1 | 15.3 | |||||
| 100 | 19 | 5,260 | 21.3 | 60 | |||||
Note 1. Industrial Relays, The rated current and coil resistance are measured at a coil temperature of 23°C with tolerances of +15%/-20% for AC rated current and ±15% for DC coil resistance. (The AC rated current is the same value for both 50 and60 Hz.)
Note 2. The coil inductance shown is a reference value.
*The figures for the operating characteristics are for a coil temperature of +23°C.
Note 4. The maximum allowable coil voltage refers to the maximum value in a varying range of operating power voltage, measured at ambient temperature 23°C.
Note 5. The "to" (for example "100 to 120") represents the range of rated voltages.
Switch (Contact) of OMRON Industrial Relays
| Format | Model G7L-1A-T□ Model G7L-1A-B□ | Model G7L-2A-T□ Model G7L-2A-B□ | Model G7L-1A-P Model G7L-2A-P | |||
|---|---|---|---|---|---|---|
| Load | Resistive Load | Inductive Load (cosø = 0.4) | Resistive Load | Inductive Load (cosø = 0.4) | Resistive Load | Inductive Load (cosø = 0.4) |
| Contact Mechanism | Double break | |||||
| Contact Material | Ag alloy | |||||
| Rated Load | 220 V AC 30 A | 220 V AC 25 A | 220 V AC 25 A | 220 V AC 20 A | ||
| Rated Carry Current | 30 A | 25 A | 0 to 20 A | |||
| Max. Contact Voltage Value | 250 V AC | |||||
| Max. Contact Current Value | 30 A | 25 A | 20 A | |||
Note: Industrial Relays, When using B-series (screw) products, since the screw diameter of the contact terminal is M4, be careful that the contact current should be 20 A or less according to JET standard (electrical appliance and material control law ofJapan).
Performance of OMRON Industrial Relays
| Contact Resistance *1 | 50 mΩ max. | |
|---|---|---|
| Operating Time *2 | 30 ms max. | |
| Recovery Time *2 | 30 ms max. | |
| Maximum Switching Frequency | Mechanical | 1,800 operations/hr |
| Rated Load | 1,800 operations/hr | |
| Insulation Resistance *3 | 1,000 MΩ min. | |
| Dielectric Strength | Between Coil and Contacts | 4,000 V AC 50/60 Hz for 1 min |
| Between Contacts of Same Polarity | 2,000 V AC 50/60 Hz for 1 min | |
| Between Contacts of Different Polarity (2a Type) | ||
| Impulse Withstand Voltage | Between Coil and Contacts: 10,000 V *4 | |
| Vibration | Durability | 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) |
| Malfunction | 10 to 55 to 10 Hz, 0.75-mm single amplitude (1.5-mm double amplitude) | |
| Shock | Durability | 1,000 m/s2 |
| Malfunction | 100 m/s2 | |
| Durability | Mechanical | 1,000,000 operations min. (at approx. 1,800 operations/h) |
| Electrical *5 | 100,000 operations min. (at 1,800 operations/hr under rated load) | |
| Failure Rate (P Level) (Reference Value *6) | 5 V DC 100 mA | |
| Weight | Approx. 90 g: (tab terminal type) | |
| Approx. 100 g: (PCB terminal type) | ||
| Approx. 120 g: (screw terminal type) | ||
| Ambient Operating Temperature | -25 to +60°C (assuming no icing or condensation) | |
| Ambient Operating Humidity | 5 to 85% RH | |
Note: The values given above are initial values of Industrial Relays.
*1. Measurement conditions: 5 V DC, 1 A, voltage drop method.
*2. Measurement conditions: Rated operating voltage applied, not including contact bounce. Ambient temperature: +23°C
*3. Measured with a 500 V DC ohmmeter at the same places that the dielectric strength was checked.
*4. JEC-212 (1981) Standard Impulse Wave Type (1.2 × 50 μs).
*5. Ambient temperature: +23°C
*6. This value was measured at a switching frequency of 60 operations/min.