MELSEC-QS Series Safety Relay Unit (for CC-Link)

:
MITSUBISHI

    A safety relay unit installable on CC-Link networks.

    MELSEC-QS Series Safety Relay Unit (for CC-Link) Specifications

    QS90SR2SN-CC

    QS90SR2SN-CC image

    QS90SR2SN-CC image

    QS90SR2SN-CC Performance Specifications

    Input Specifications
    Number of Safety Inputs1 safety input (2 inputs)
    Number of Other Inputs1 inrush input
    Safety Input Rated Input Voltage24 V DC (ripple ratio: within 5%) (allowable voltage range: 20.4 to 26.4 V DC)
    Safety Input Rated Input Current4.6 mA (300 mA when starting relay)
    Input FormatTypeN type
    X0Positive common
    X1Negative common
    Input Insulation MethodRelay insulation
    Input Common MethodNo common (All independent points)
    Output Specifications
    Number of Safety Output Points1 safety output point (3 outputs)
    Rated Load CurrentCategory 4: 3.6 A / point or less
    (Category 3: 5.0 A / point or less)
    Minimum Switching Load5 V DC 5 mA
    Maximum Permissible Contact Voltage250 V AC, 30 V DC
    Resistant Load250 V AC / 5 A, 30 V DC / 5 A
    Lifespan of RelayMechanical5 million times or more
    Electrical100,000 times or more
    Maximum Switching Frequency1,200 times / hour at rated control capacity
    Response TimeOutput Operating Time50 ms or less (safety input ON > safety output ON)
    Output Shutdown Time20 ms or less (safety input OFF > safety output OFF)
    Output Insulation MethodRelay insulation
    Output Common MethodNo common (All independent points)
    Common Specifications
    Number of Units for ExpansionUp to 3 expansion safety relay units can be connected
    Dielectric StrengthSafety output between different poles: 2,500 V AC at 1 mA or less for 1 minute
    Between safety input and safety output: 2,500 V AC at 1 mA or less for 1 minute
    Between power supply and safety output: 2,500 V AC at 1 mA or less for 1 minute
    Insulation ResistanceSafety output between different poles: 100 MΩ or more with 500 V DC ohmmeter
    Between safety input and safety output: 100 MΩ or more with 500 V DC ohmmeter
    Between power supply and safety output: 100 MΩ or more with 500 V DC ohmmeter
    Station TypeRemote I/O stations
    Number of Occupied Stations1 station
    Unit Power SupplyVoltage24 V DC (ripple ratio: within 5%) (allowable voltage range: 20.4 to 26.4 V DC)
    Current70 mA (without expansion unit), 145 mA (with 3 expansion units)
    Safety Power SupplyVoltage24 V DC (ripple ratio: within 5%) (allowable voltage range: 20.4 to 26.4 V DC)
    Current85 mA (without expansion unit), 325 mA (with 3 expansion units)
    Protection GradeIP1X
    External Wiring Connection Method2-piece spring clamp terminal block
    Communication CableDedicated CC-Link cable compatible with Ver. 1.10
    Dedicated CC-Link cable (compatible with Ver. 1.00)
    Dedicated CC-Link high-performance cable (compatible with Ver. 1.00)
    External DimensionsHeight (H)112 mm
    Width (W)45 mm
    Depth (D)113.5 mm
    Weight0.37 kg

    QS90SR2SN-CC General Specifications

    Ambient Operating Temperature0 to 55°C
    Ambient Storage Temperature-20 to 75°C
    Ambient Operating Humidity30 to 85% RH, non-condensing
    Ambient Storage Humidity30 to 85% RH, non-condensing
    Vibration ResistanceJIS B 3502, IEC 61131-2 CompliantUnder Intermittent VibrationFrequency: 5 to 8.4 Hz, Single amplitude: 3.5 mm
    Frequency: 8.4 to 150 Hz; Constant acceleration: 9.8 m/s2
    Number of sweeps: 10 times in each direction of X, Y and Z
    Under Continuous VibrationFrequency: 5 to 8.4 Hz, Single amplitude: 1.75 mm
    Frequency: 8.4 to 150 Hz, Constant acceleration: 4.9 m/s2
    Impact ResistantJIS B 3502, IEC 61131-2 compliant (147 m/s2, for a duration of 11 ms, 3 times in 3 directions of X, Y and Z with a half-sine pulse)
    Operating AtmosphereNo corrosive gases
    Operating Altitude0 to 2,000 m
    Installation LocationInside the control panel with IP54 or higher
    Overvoltage CategoryIII or lower
    Pollution Degree2 or less
    Equipment ClassClass I