MELSEC-F Series Display Module

:
MITSUBISHI

    MELSEC-F Series Display Module.
    [Features]
    · The monitor settings make easy operation at a reasonable cost possible.
    · Can be connected to a sequencer with 1 cable. (FX-10DM-SET0)
    · Can be mounted directly, with no need for wiring. (FX3G-5DM/FX3U-7DM)
    [Applications]
    · For machine startup, adjustment, and program changing.

    Display Module FX-10DM-SET0 Features

    Can be mounted on a surface and connected to a sequencer with a cable.
    When used with a registration monitor, up to 8 frequently used devices can be registered easily.
    Comments and messages can be displayed in an easy-to-see manner in the display content.

    FX-10DM-SET0 Specifications

    FunctionData Change FunctionsCurrent Value ChangeChanges Current T, C, and D Values
    Setting Value ChangeChanges Current T and C Values
    Reset FunctionReset Current T, C, and D Values to 0
    Device Monitoring FunctionWord Device (16‑Bit)Displays T and C current values / setting values and D current value.
    Word Device (32‑Bit)32‑bit counter displays C current value / setting value and D current value.
    Registration Monitor FunctionA Function for registering in advance up to 8 lines of devices and messages to display
    Message Display FunctionDisplays ASCII code saved to the sequencer data register.
    Display content can be switched from the sequencer.
    · Up to 16 single-byte characters per line
    · Displays letters, numbers, Japanese Kana and symbols.
    Comment FunctionDisplays device monitors and registration monitor screen word device names in the comments in the sequencer.
    · 8 single-byte characters per line for 16‑bit, 4 characters per line for 32‑bit
    · Displays letters, numbers, Japanese Kana and symbols.
    Buzzer SoundCan be set ON/OFF.
    System LanguageJapanese/English switchable
    Performance SpecificationsDust-Proof, WaterproofThe operation panel screen has a dustproof and water-proof construction equivalent to IP65f (compliance checked in IP65f testing, but this test does not guarantee the use in all environments).
    Connectable SequencersFX1S, FX3S, FX1N, FX3G, FX2N, FX3U, FX1NC, FX3GC, FX2NC, FX3UC
    FX3S, FX3G, and FX3GC are treated as FX1N devices.
    FX3U and FX3UC are treated as FX2N devices.

    Display Module FX3G-5DM Features And External Diagram

    Can be mounted directly on the FX3G sequencer, with no need for wiring.
    Utilizes a maintenance-free green LED backlight.
    Comes with an "Operator function" allowing operation with the keys only, and a "Control function" for control via sequences.
    Can be used with a function extension board.

    FX3G-5DM

    FX3G-5DM

    FX3G-5DM Specifications

    FunctionMonitor/TestInput (X), Output (Y), Auxiliary Relay (M), State (S), Timer (T), Counter (C), Data Register (D) [16‑bit/32‑bit], Expansion Register (R) [16‑bit/32‑bit], Expansion File Register (ER) [16‑bit/32‑bit] Monitor/Test Functions
    *There is no test function for input (X).
    Error CheckA function that performs an error check and displays the results
    LANGUAGESets the Menu Display Language to Japanese or English.
    Contrast AdjustmentAdjusts the contrast (-5 to 10). Default value: 0
    Time SettingCurrent TimeDisplays the current time.
    Time ChangeSets the current time.
    KeywordCan unlock the set keyword.
    Memory Cassette TransferData can be transferred between the internal EEPROM and a memory cassette.
    Designated Device Monitor FunctionDisplays the monitor/test screen of the designated device on the top screen.
    Screensaver FunctionDisplays a screen saver when no keys are used for a specified time.
    Display Screen Protection FunctionCan protect all functions valid, change (test) function prohibited and top screen (time display).
    Operation Button ON/OFF InformationAllows monitoring of the ON/OFF state of operation buttons.
    Current Value Hexadecimal Display SettingsChanges current and set values of times, counters, data registers, expansion registers and expansion file registers to hexadecimal display.
    *A sequence program is needed to display the current values for timer (T), counter (C), data register (file register) (D) [16‑bit/32‑bit], expansion register (R) [16‑bit/32‑bit], and expansion file register (ER) [16‑bit/32‑bit] as hexadecimal values.
    Display/Switch SpecificationsDisplay ElementsSTN Monochrome Liquid Crystal
    BacklightGreen LED Backlight
    Display TextNumber Of CharactersFour Lines of 16 Single-byte Characters
    TextSingle-byte Alphanumerics, Katakana
    Menu Display LanguageJapanese/English
    Switches (Operation Button)4 (OK, ESC, +, -)
    Performance SpecificationsConnectable SequencersFX3G

    Display Module FX3U-7DM Features And External Diagram

    A holder (1.4 m cable included) for attaching FX3U-7DM type display modules to the panel.
    Attachment to a panel door, etc., allows monitoring/testing the device and checking the display screen without opening the door, etc.

    FX3U-7DM

    FX3U-7DM

    FX3U-7DM Specifications

    FunctionMonitor/TestDeviceInput (X), Output (Y), Auxiliary Relay (M), State (S), Timer (T), Counter (C), Data Register (D) [16‑bit/32‑bit], Expansion Register (R) [16‑bit/32‑bit], Expansion File Register (ER)[16‑bit/32‑bit] Monitor/Test Functions
    *There is no test function for input (X).
    User Registration DeviceUp to four data registers (D) [16‑bit/32‑bit] can be registered (a program required).
    Error CheckA function that performs an error check and displays the results
    LANGUAGE (Menu Display Language Setting)Sets the Menu Display Language to Japanese or English.
    Contrast AdjustmentAdjusts the contrast (-5 To 10). Default value: 0
    Time SettingSettingSets the current time.
    DisplayDisplays the current time.
    KeywordCan unlock the set keyword.
    Device All ClearA function for initializing Input (X), Output (Y), Auxiliary Relay (M), State (S), Timer (T), Counter (C), Data Register (D) and Expansion Register (R).
    However, this does not include the file register (D).
    (Sets bit device to OFF, and word device current value to 0.)
    PC InformationA function for checking version information, keyword state, program memory type and state, and battery voltage, etc.
    Scan Time DisplayDisplays scan time (maximum/minimum/current values).
    Memory Cassette TransferData can be transferred/collated between internal RAM and a memory cassette.
    Operation Button ON/OFF InformationAllows monitoring of the ON/OFF state of operation buttons (a program required).
    Current Value Hexadecimal Display SettingsChanges current values / setting values for timers, counters, data registers, expansion registers and expansion file registers to hexadecimal values (a program required).
    Display Screen Protection FunctionCan protect all functions valid, change (test) function prohibited and top screen (time display) (a program required).
    User Message DisplayCan issue display commands for the following codes stored in display devices.
    Single-byte alphanumerics: 20H To 7DH ASCII codes
    Katakana: A1H To DFH ASCII code
    Japanese: SHIFT JIS Code (standards 1 and 2)
    (a program required)
    Performance SpecificationsConnectable SequencersFX3U, FX3UC-32MT-LT(-2)
    <Caution>
    FX3UC-32MT-LT(-2) features FX3U-7DM as standard equipment.

    Display Module Holder FX3U-7DM-HLD Features And External Diagram

    A holder (1.4‑m cable included) for attaching FX3U-7DM type display modules to a panel.
    Attachment to a panel door, etc., allows monitoring/testing the device and checking the display screen without opening the door, etc.

    X3U-7DM-HLD

    X3U-7DM-HLD