Molded Case Circuit Breakers (MCCB) NF-CV/SV

:
MITSUBISHI

    · Molded Case Circuit Breakers (MCCB) NF-CV/SV series from MITSUBISHI.
    · Rated Current Range: 3.4A to 63A (varies by model)
    · Number of Poles: 2, 3, or 4 (model-dependent)
    · Rated Insulation Voltage: 500V or 600V (model-dependent)
    · Rated Short-Circuit Breaking Capacity: AC voltages: 230V to 690V, DC voltage: 250V (for some models)
    · Short-Circuit Breaking Capacity Range: 2.5/2.5 kA to 75/75 kA (varies by voltage and model)
    · Standard Attached Parts: Terminal screw: M5×14, Mounting screw: M4×0.7×55 and Insulation barrier

    NF-MB Type MCCB for MITSUBISHI Circuit Breakers Protection: Specification Table

    Frame A303250100
    Circuit Breakers ModelNF32-SVNF63-CVNF63-SVNF-125-SV
    Number of Poles33333
    Rated Insulation Voltage Ui (V)500500500500500
    Rated
    Short
    Circuit
    Breaking
    Capacity
    (kA)


    JIS C 8201-2-1 Ann.1
    JIS C 8201-2-1 Ann.2
    IEC 60947-2
    EN 60947-2
    (Icu/Ics)
    AC440 V2.5/2.52.5/2.52.5/2.57.5/7.525/25
    415 V2.5/2.52.5/2.52.5/2.57.5/7.530/30
    400 V5/55/55/57.5/7.530/30
    380 V5/55/55/57.5/7.530/30
    230 V7.5/7.57.5/7.57.5/7.515/1550/50
    GB 14048.2
    (Icu/Ics)
    AC415 V2.5/2.52.5/2.52.5/2.57.5/7.530/30
    400 V5/55/55/57.5/7.530/30
    380 V5/55/55/57.5/7.530/30
    230 V7.5/7.57.5/7.57.5/7.515/1550/50
    NK
    (Icu/Ics)
    AC450 V2.5/2.52.5/2.52.5/2.57.5/7.525/25
    240 V7.5/7.57.5/7.57.5/7.515/1550/50
    Rated Impulse Withstand Voltage Uimp (kV)88888
    Circuit Breakers Current TypeACACACACAC
    Isolation CompatibilityCompatibleCompatibleCompatibleCompatibleCompatible
    Reverse ConnectionPossiblePossiblePossiblePossiblePossible
    Open-close Lifespan (Cycles)Mechanical10,00010,00010,00015,00025,000
    Electrical (440 V AC)6,0006,0006,0008,00010,000
    Selectability Type (Usage Category)AAAAA
    Degree of Contamination33333
    EMC Environmental Conditions (Environment A or Environment B)N/AN/AN/AN/AN/A
    External
    Dimensions
    (mm)

    a7575757590
    b130130130130130
    c6868686868
    ca9090909090
    Product Weight of Front Surface Type (kg)0.650.650.650.71.0
    Electrical Appliance and Material Safety ActCompatibleCompatibleCompatibleCompatibleCompatible
    CE MarkSelf-declaredSelf-declaredSelf-declaredSelf-declaredSelf-declared
    CCC CertificationCertifiedCertifiedCertifiedCertifiedCertified
    Classification Society Certification (✓ = Acquired) (NK, LR, ABS, DNV/GL)
    Overcurrent Tripping MethodThermal - electromagneticThermal - electromagneticThermal - electromagneticThermal - electromagneticThermal - electromagnetic
    Trip Button

    Note 1: The rated capacity applicable to the motor is not stated on the Circuit Breakers. It should be selected according to the full-load current of the motor.
    Note 2: Please specify "FP-LT" for flush type with lead terminal block.
    Note 3: Please specify "P-LT" for plug-in type with lead terminal block.

    External Dimensions of Circuit Breakers

    External dimensions

    Rated Capacity for MITSUBISHI Circuit Breakers

    Circuit Breakers NF32-SV (Frame A: 30)

    A200/220 V400/440 V
    kWkW
    255.511
    163.77.5
    12-5.5
    102.2-
    8-3.7
    7.11.5-
    5-2.2
    40.751.5

    Circuit Breakers NF63-CV

    A200/220 V400/440 V
    kWkW
    451122
    40-18.5
    327.515
    255.511
    163.77.5
    12-5.5
    102.2-
    8-3.7

    Circuit Breakers NF32-SV (Frame A: 32)

    A200/220 V400/440 V
    kWkW
    327.515

    Circuit Breakers NF63-SV

    A200/220 V400/440 V
    kWkW
    7.11.5-
    5-2.2
    40.751.5

    Circuit Breakers NF125-SV

    A200/220 V400/440 V
    kWkW
    100-55
    902245
    7118.537
    631530
    451122
    (40)-19
    327.515
    (25)5.511
    (16)3.77.5
    (12.5)-5.5

    Rated current: A
    Rated capacity for Circuit Breakers: kW
    Standard ambient temperature: 40°C (45°C for ships)