MELSEC-Q Series Power Supply Unit (Normal Type)

:
MITSUBISHI

    Power supply unit for the versatile model MELSEC-Q Series.
    [Features]
    · Supplies power to the CPU unit, input/output unit and various other units.
    · External dimensions: (H) 98 mm, (W) 55.2 mm, (D) 90 mm.
    [Applications]
    · Power supply to unit.

    Power Supply Unit Q61P Specifications

    Base Installation PositionInstallation slot for power supply unit
    Compatible Base UnitQ3□B, Q3□DB, Q6□B
    Input Power Supply Voltage100 to 240 V AC (-15% to +10%)
    Input Frequency50/60 Hz ±5%
    Input Voltage Distortion FactorWithin 5%
    Input Maximum Apparent Power130 V A
    Inrush CurrentWithin 20 A, 8 ms
    Rated Output Current5 V DC6 A
    Overcurrent Protection5 V DC6.6 A or more
    Overvoltage Protection5 V DC5.5 to 6.5 V
    Efficiency70% or more
    Allowable Momentary Power Loss TimeWithin 20 ms
    Withstand VoltageBetween all inputs / LG at once and all outputs / FG at once 2,300 V AC / 1 minute (altitude 0 to 2,000 m)
    Insulation ResistanceBetween all inputs / LG at once and all outputs / FG at once, between all inputs at once and LG, between all outputs at once and FG: 10 MΩ or more at 500 V DC on an insulation resistance tester
    Operation IndicationLED indication (Normal: green light is lit, Error: unlit)
    FuseBuilt-in (not user-replaceable)
    Contact Output PartApplicationsERR contact
    Rated Opening/Closing Voltage/Current24 V DC, 0.5 A
    Minimum Switching Load5 V DC 1 mA
    Response TimeOFF > ON10 ms or less
    ON > OFF12 ms or less
    LifespanMechanical20 million times or more
    ElectricalRated opening/closing voltage / current load: 100,000 times or more
    Surge SuppressorN/A
    FuseN/A
    External Wiring Connection MethodScrew terminal block (M3.5 screw)
    External DimensionsHeight (H)98 mm
    Width (W)55.2 mm
    Depth (D)90 mm
    Weight0.40 kg

    Power Supply Unit Q63P Specifications

    Base Installation PositionInstallation slot for power supply unit
    Compatible Base UnitQ3□B, Q3□DB, Q6□B
    Input Power Supply Voltage24 V DC (-35% to +30%)
    Input Maximum Power45 W
    Inrush CurrentWithin 100 A / 1 ms (at 24 V DC input)
    Rated Output Current5 V DC6 A
    Overcurrent Protection5 V DC6.6 A or more
    Overvoltage Protection5 V DC5.5 to 6.5 V
    Efficiency70% or more
    Allowable Momentary Power Loss TimeWithin 10 ms (at 24 V DC input)
    Withstand VoltageBetween all inputs / LG at once and all outputs / FG at once 510 V AC / 1 minute (altitude 0 to 2,000 m)
    Insulation Resistance10 MΩ or more with insulation resistance tester
    Operation IndicationLED indication (Normal: green light is lit, Error: unlit)
    FuseBuilt-in (not user-replaceable)
    Contact Output PartApplicationsERR contact
    Rated Opening/Closing Voltage/Current24 V DC, 0.5 A
    Minimum Switching Load5 V DC 1 mA
    Response TimeOFF > ON10 ms or less
    ON > OFF12 ms or less
    LifespanMechanical20 million times or more
    ElectricalRated opening/closing voltage/current load: 100,000 times or more
    Surge SuppressorN/A
    FuseN/A
    External Wiring Connection MethodScrew terminal block (M3.5 screw)
    External DimensionsHeight (H)98 mm
    Width (W)55.2 mm
    Depth (D)90 mm
    Weight0.33 kg