MELSEC-Q Series High Speed Data Logger Unit

:
MITSUBISHI

    MELSEC-Q Series High-speed Data Logger Unit.
    [Features]
    · Supports various logging needs requiring no personal computer.
    · Capable of high-speed, simple and unprecedentedly accurate data logging at low cost.
    · External dimensions: (H) 98 mm, (W) 27.4 mm, (D) 90 mm.
    [Applications]
    · Used for data logging.

    High-Speed Data Logger Unit QD81DL96 Performance Specifications

    Software Specifications

    Data AcquisitionNumber of Accessed CPUsMaximum 64
    Acquisition IntervalHigh-Speed Acquisition· Sequence Scan Time Synchronization
    · 1 to 32,767 ms (for trigger logging)
    · 3 to 32,767 ms (for continuous logging)
    General-Purpose Acquisition· 0.1 to 0.9 s, 1 to 32,767 s
    · Time interval specification (hour/minutes/seconds specification)
    Number of Acquired DataHigh-Speed Acquisition· Total number of data: max. 8,192 (256 per setting)
    · Total number of device points: max. 8,192 (256 per setting)
    General-Purpose Acquisition· Total number of data: maximum 16,384 (256 per setting)
    · Total number of device points: maximum 262,144 (4,096 per setting)
    Data Types· Bit
    · Word (signed)
    · Double words (signed)
    · Word (unsigned)
    · Double words (unsigned)
    · Single-precision real number
    · Double-precision real number
    · 16-bit BCD
    · 32-bit BCD
    · Character string: 1 to 8,192 characters
    · Numerical string: 1 to 8,192 bytes
    Data Output Format (CSV File)· Bit
    · Decimal: 0 to 14 decimal digits
    · Exponential: 0 to 14 decimal digits
    · Hexadecimal
    · Character string
    · Numerical string
    ScalingArithmetic operations: operations combining (×, /) and (+, -)
    Data LoggingNumber of SettingsMaximum 64
    Logging Types· Continuous logging
    · Trigger logging
    File Format· CSV File (Extension: .CSV)
    · Binary File (Extension: .BIN)
    PeriodSpecify the applicable period or excluded period.
    · Data conditions: bit ON/OFF, comparison of data against a constant value, comparison of data against data
    · Date range: specification of starting and ending months/days
    · Time range: specification of starting and ending hour/minutes/seconds
    · Day of week / week conditions: specification of day of the week or a week
    AND or OR of the above: up to 8 conditions
    Trigger LoggingTrigger Conditions· Condition:
     · Comparison: bit ON/OFF, comparison of data against a constant value, comparison of data against data
    · Change in value
    · Constant cycle: 1 to 86,400 s
    · Time interval specification: specification of hour/minutes/seconds
    · Time specification: specification of month/day/hour/minutes/seconds
    · Startup of unit
    AND or OR of the above (for up to 8 conditions).
    · Number of conditions established: 3 conditions
    · Condition establishment order (order and time condition): up to 4 conditions
    Number of Logging Lines· Before trigger: 0 to 65,534 lines
    · After trigger: 1 to 65,535
    Up to 65,535 lines as a total of the above before and after trigger
    File Switching Timing· Specification of number of lines (number of records): 100 to 100,000 lines
    · Specification of file size: 10 to 16,384 KB
    · Condition specification:
     · Comparison: bit ON/OFF, comparison of data against a constant value, comparison of data against data
    · Change in value
    · Constant cycle: 1 to 86,400 s
    · Time interval specification: specification of hour/minutes/seconds
    · Time specification: specification of month/day/hour/minutes/seconds
    · Startup of unit
    AND or OR of the above: up to 8 conditions
    · Trigger logging unit
    Number of Saved Files1 to 65,535
    ReportNumber of SettingsMaximum 64
    File FormatExcel® File (Extension: .xls)
    Output Data Types· Data in the data logging file
    · Present value data
    · Time created
    Number of Output Data64 layouts per report setting, for total 65,535 cells
    Creation Trigger Conditions· Condition:
     · Comparison: bit ON/OFF, comparison of data against a constant value, comparison of data against data
    · Change in value
    · Constant cycle: 1 to 86,400 s
    · Time interval specification: specification of hour/minutes/seconds
    · Time specification: specification of month/day/hour/minutes/seconds
    · Startup of unit
    · Data logging file switching
    AND or OR of the above (up to 8 conditions)
    · Number of conditions established: 3 conditions
    · Condition establishment order (order and time condition): up to 4 conditions
    PeriodSpecify the applicable period or excluded period.
    · Data conditions: bit ON/OFF, comparison of data against a constant value, comparison of data against data
    · Date range: specification of starting and ending months/days
    · Time range: specification of starting and ending hour/minutes/seconds
    · Day of week / week conditions: specification of day of the week or a week
    AND or OR of the above: up to 8 conditions
    Layout File SizeMaximum 10 M bytes (total of all report settings)
    Number of Saved Files1 to 65,535
    EmailApplications· Event notification
    · Saved file transmission
    Subject· Event notification email: user-specified
    · Saved file transmission email: automatically generated / user-specified
    Main Text· Event notification email: user-specified
    · Saved file transmission email: automatically generated / user-specified
    Attachment File· Event notification email: none
    · Saved file transmission email: saved file (CSV, binary, Excel file), maximum 512 K bytes
    Attachment File FormatMIME format
    MIMEVersion 1.0
    Communication With Mail ServerPort Number25, 587, Other (1 to 65,535)
    Authentication Method· No Authentication
    · SMTP-AUTH (PLAIN, LOGIN, CRAM-MD5)
    · POP before SMTP
    Recipient AddressMaximum 16 groups
    Validated Email Client Software· Microsoft® Outlook® Express 6.0
    · Microsoft® Windows® Mail 6.0
    FTP ServerApplicationsRead/delete saved files, write/read/delete recipe files
    Validated FTP Client Software· Microsoft® Internet Explorer® 6.0
    · Windows® Internet Explorer® 7.0
    · Windows® Internet Explorer® 8.0
    · Windows® Internet Explorer® 9.0
    · Windows® Internet Explorer® 10.0
    · Windows® Internet Explorer® 11.0
    Number of Sessions10
    FTP ClientApplicationsSaved file transfer
    Validated FTP Server SoftwareMicrosoft®Internet Information Service
    RecipeNumber of DataMaximum 256 data
    Number of RecordsMaximum 256 records
    Data Types· Bit
    · Word [signed]
    · Double words [signed]
    · Word [unsigned]
    · Double words [unsigned]
    · Single-precision real number
    · Double-precision real number
    · 16-bit BCD
    · 32-bit BCD
    Recipe FileCSV File (Extension: CSV)
    Maximum 256 files
    Execution TypeDedicated commands (ladder programs), setting tools

    Hardware Specifications

    Ethernet PartInterface10BASE-T/100BASE-TX
    Communication MethodFull-duplex / Half-duplex communication mode
    Flow ControlFull duplex communication: none (IEEE802.3x flow control is not supported)
    Half duplex communication: back pressure
    Data Transmission Speed10 Mbps(10BASE-T)/100 Mbps(100BASE-TX)
    Transmission MethodBaseband
    Number of Cascade Connection LevelsMaximum 4 levels (10BASE-T) / Maximum 2 levels (100BASE-TX)
    Maximum Segment Length100 m
    Support FunctionAutomatic negotiation function (Automatic recognition of communication speed / communication method)
    Compact Flash Card PartSupplied Power CapacityMaximum 150 mA
    Card SizeTYPE I card
    Supplied Power Voltage3.3 V ±5%
    Installable Quantity1 pc.
    Number of Occupied Inputs/Outputs32 points (I/O assignment: intelligent 32 points)
    Clock· Obtained from the sequencer CPU (first CPU unit in the case of a multi-CPU system) or SNTP server
    · Once the clock data is obtained, the clock has a daily variance of ±9.504 seconds
    5 V DC Internal Current Consumption0.50 A
    External DimensionsHeight (H)98 mm
    Width (W)27.4 mm
    Depth (D)90 mm
    Weight0.15 kg