MELSEC-Q Series Sequencer CC-Link System Master / Local Unit

:
MITSUBISHI

    · Cost-effective field network with broad device compatibility.
    · Supports high-speed data transfer for both bit data (ON/OFF status) and word data.
    · Ensures consistent cyclic transmission by separating it from message communication, preventing delays even during high message traffic.
    · Compatible with CC-Link versions 1 and 2.
    · Can function as either a local or master module, providing flexible network configuration.
    · Ideal for maintaining punctual link scan times, unaffected by message saturation.

    CC-Link System Master / Local Unit QJ61BT11N

    Outline drawing

    MELSEC-Q Series CC-Link System Master / Local Unit: related image

    Outline drawing (unit: mm)

    Performance Specifications

    Transmission Speed156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps (Selectable)
    Maximum Total Cable Extension (Maximum Transmission Distance)Ver. 1.10At 156 kbps1,200 m
    At 635 kbps900 m
    At 2.5 Mbps400 m
    At 5 Mbps160 m
    At 10 Mbps100 m
    Station TypeMaster Station (Ver. 1 Master Station or Ver. 2 Master Station)
    Local Station (Ver. 1 Local Station or Ver. 2 Local Station)
    Maximum Number Of Connected DevicesMaster Station64 devices
    Number Of Occupied StationsLocal Station1 to 4 stations
    Maximum Link Points Per SystemCC-Link Ver. 1Remote inputs/outputs (RX, RY): 2,048 points
    Remote registers (RWw): 256 points
    Remote registers (RWr): 256 points
    CC-Link Ver. 2Remote inputs/outputs (RX, RY): 8,192 points
    Remote registers (RWw): 2,048 points
    Remote registers (RWr): 2,048 points
    Link Points Per StationCC-Link Ver. 1Remote inputs/outputs (RX, RY): 32 points (30 points for local stations)
    Remote registers (RWw): 4 points
    Remote registers (RWr): 4 points
    CC-Link Ver. 2Expanded Cyclic Setting: × 1 SettingRemote inputs/outputs (RX, RY): 32 points (30 points for local stations)
    Remote registers (RWw): 4 points
    Remote registers (RWr): 4 points
    Expanded Cyclic Setting: × 2 SettingRemote inputs/outputs (RX, RY): 32 points (30 points for local stations)
    Remote registers (RWw): 8 points
    Remote registers (RWr): 8 points
    Expanded Cyclic Setting: × 4 SettingRemote inputs/outputs (RX, RY): 64 points (62 points for local stations)
    Remote registers (RWw): 16 points
    Remote registers (RWr): 16 points
    Expanded Cyclic Setting: × 8 SettingRemote inputs/outputs (RX, RY): 128 points (126 points for local stations)
    Remote registers (RWw): 32 points
    Remote registers (RWr): 32 points
    Communication MethodBroadcast polling method
    Synchronization MethodFrame Synchronization Method
    Encryption MethodNRZI (Non Return to Zero Inverted) sign
    Transmission Path TypeBus (RS-485)
    Transmission FormatHDLC Compliant
    Error Control MethodCRC (X16 + X12 + X5 + 1)
    Communication CableDedicated CC-Link cable compatible with Ver. 1.10
    Dedicated CC-Link cable (compatible with Ver. 1.00)
    Dedicated CC-Link high-performance cable (compatible with Ver. 1.00)
    Number Of Occupied Inputs/Outputs32 points (I/O assignment: Intelligent 32 points)
    5 V DC Internal Current Consumption0.46 A
    External DimensionsHeight (H)98 mm
    Width (W)27.4 mm
    Depth (D)90 mm
    Mass0.12 kg