MELSEC-Q Series AC Input Unit

:
MITSUBISHI

    MELSEC-Q series AC input unit.
    [Features]
    · A wider range of lineup than the common type in voltage and number of input points.
    · External dimensions: (H) 98 mm, (W) 27.4 mm, (D) 90 mm.
    [Applications]
    · For receiving external ON/OFF signals and transmitting ON/OFF signals externally.

    AC Input Unit QX10/QX10-TS Common Specifications

    Input FormatAC Input
    Number of Inputs16 points
    Rated Input Voltage, Frequency100 to 120 V AC (+10/-15%), 50/60 Hz(±3 Hz)
    Input Voltage Distortion FactorWithin 5%
    Rated Input CurrentApprox. 8 mA (for 100 V AC, 60 Hz)
    Approx. 7 mA (for 100 V AC, 50 Hz)
    Inrush CurrentMaximum 200 mA, within 1 ms (for 132 V AC)
    ON Voltage / ON Current80 V AC or more / 5 mA or more (50 Hz, 60 Hz)
    OFF Voltage / OFF Current30 V AC or less / 1.7 mA or less (50 Hz, 60 Hz)
    Input ImpedanceApprox. 12 kΩ (60 Hz), approx. 15 kΩ (50 Hz)
    Input Response TimeOFF > ON15 ms or less (100 V AC 50 Hz, 60 Hz)
    ON > OFF20 ms or less (100 V AC 50 Hz, 60 Hz)
    Input Common Method16 points 1 common
    Insulation MethodOpto-isolator insulation
    Dielectric Strength1,780 V AC rms / 3 cycles (altitude 2,000 m)
    Insulation Resistance10 MΩ or more on an ohmmeter
    Operation DisplayON Display (LED)
    Number of Occupied Inputs/Outputs16 points (I/O assignment: input 16 points)
    5 V DC Internal Current Consumption50 mA (TYP. all points ON)
    External DimensionsHeight (H)98 mm
    Width (W)27.4 mm
    Depth (D)90 mm
    Weight0.17 kg

    Input Derating

    Input Derating

    Input Derating

    Protection Grade / External Wiring Connection Method

    QX10 protection grade: IP1X / external wiring connection method: 18-point screw terminal block (M3 screw)
    QX10-TS protection grade: IP2X / external wiring connection method: 18-point 2-piece spring clamp terminal block

    AC Input Unit QX28 Specifications

    Input FormatAC Input
    Number of Inputs8 points
    Rated Input Voltage, Frequency100 to 240 V AC (+10/-15%), 50/60 Hz(±3 Hz)
    Input Voltage Distortion FactorWithin 5%
    Rated Input CurrentApprox. 17 mA (200 V AC, 60 Hz)
    Approx. 14 mA (200 V AC, 50 Hz)
    Approx. 8 mA (100 V AC, 60 Hz)
    Approx. 7 mA (100 V AC, 50 Hz)
    Inrush CurrentMaximum 950 mA, within 1 ms (for 264 V AC)
    ON Voltage / ON Current80 V AC or more / 5 mA or more (50 Hz, 60 Hz)
    OFF Voltage / OFF Current30 V AC or less / 1.7 mA or less (50 Hz, 60 Hz)
    Input ImpedanceApprox. 12 kΩ (60 Hz), approx. 15 kΩ (50 Hz)
    Input Response TimeOFF > ON10 ms or less (100 V AC 50 Hz, 60 Hz)
    ON > OFF20 ms or less (100 V AC 50 Hz, 60 Hz)
    Input Common Method8 points 1 common
    Insulation MethodOpto-isolator insulation
    Dielectric Strength2,830 V AC rms / 3 cycles (altitude 2,000 m)
    Insulation Resistance10 MΩ or more on an ohmmeter
    Protection GradeIP1X
    Operation DisplayON Display (LED)
    External Wiring Connection Method18-point screw terminal block (M3 Screw)
    Number of Occupied Inputs/Outputs16 points (I/O assignment: input 16 points)
    5 V DC Internal Current Consumption50 mA (TYP. all points ON)
    External DimensionsHeight (H)98 mm
    Width (W)27.4 mm
    Depth (D)90 mm
    Weight0.20 kg

    Input Derating

    Input Derating

    Input Derating