MELSEC-F Series Temperature Sensor / Temperature Adjustment

:
MITSUBISHI

    MELSEC-F series analog input adapter for temperature sensor / temperature adjustment block.
    [Features]
    · A platinum resistance temperature sensor or a thermocouple temperature sensor can be connected.
    · Allows for input to 4 channels.
    [Applications]
    · Convenient for connecting and measuring with a temperature sensor.

    Features and Drawings of Temperature Sensor Analog Input Adapter

    MELSEC-F Series Temperature Sensor Analog Input Adapter / Temperature Control Block: related image

    Drawing

    • Temperature sensor analog input adapter for platinum resistance temperature detector (Pt100, 3-wire type) (FX3U-4AD-PT-ADP/FX3U-4AD-PTW-ADP).
    • Temperature sensor analog input adapter for thermocouple (type K, type J) temperature (FX3U-4AD-TC-ADP).
    • Four input channels are supported.
    • Measured temperatures can be indicated in Celsius (°C) or Fahrenheit (°F).
    • Data transfer is possible with no programming (dedicated commands) required.

    Temperature Sensor Analog Input Adapter Specifications

    Type NameFunctionCurrent Consumption
    5 V DCInternal 24 V DCExternal 24 V DC
    FX3U-4AD-PT-ADPPt100 type temperature sensor adapter (FX3U-□□□-BD required) -50 to 250°C15 mA0 mA50 mA
    FX3U-4AD-PTW-ADPPt100 type temperature sensor adapter (FX3U-□□□-BD required) -100 to 600°C15 mA0 mA50 mA
    FX3U-4AD-TC-ADPThermocouple temperature sensor adapter (FX3U-□□□-BD required)15 mA0 mA45 mA

    Features and Drawings of Temperature Control Block

    MELSEC-F Series Temperature Sensor Analog Input Adapter / Temperature Control Block: related image

    Drawing

    • Four channels of temperature sensor input, low-voltage signal input and control output are combined into a single unit, to achieve "2-position control, standard PID control (auto tuning is possible), heating/cooling PID control, and cascade control."
    • Cascade control using 2 master/slave control loops permits quick temperature control in response to temperature shift caused by external disturbance, etc.
    • Heating/cooling PID control can be performed using one unit, allowing for both heating output and cooling output, which enabling up to 4 loops of heating/cooling control by operating both heating output and cooling output.
    • 13 types of thermocouple sensors and 3 types of Pt sensors (Pt100, JPt100, Pt1000) can be connected.

    Temperature Control Block Specifications

    Type NameFunction5 V DC
    Current Consumption
    24 V DC Current Consumption (Power)Number of Occupied Inputs/OutputsTotal Number of Input/Output Points
    External Power SupplyInternal Power SupplyInputCommon to Input/OutputOutput
    FX3U-4LC4 ch Temperature Control Block160 mA50 mA--8-8