MELSEC-L Series Positioning Unit (Open Collector Output)

:
MITSUBISHI

    Positioning unit (open collector output) for the standard model MELSEC-L series

    MELSEC-Q Series Positioning Unit (Open Collector Output Type) Specifications

    LD75P4 image

    LD75P4 image

    Performance Specifications

    Number of Control Axis4 axes
    Interpolation Function2-axis, 3-axis, 4-axis linear interpolation
    2-axis circular interpolation
    3-axis helical interpolation
    Control MethodPTP (point to point) control
    Path control (linear, arc and helical)
    Speed control
    Speed/position switching control
    Position/speed switching control
    Single Control Unitmm, inch, degree, pulse
    Positioning Data600 data/axis
    BackupParameters, positioning data and block start data can be saved to the flash ROM (battery-less)
    PositioningPositioning MethodPTP ControlIncrement/absolute
    Speed/Position Switching ControlIncrement/absolute
    Position/Speed Switching ControlIncrement
    Path ControlIncrement/absolute
    Positioning RangeAbsolute-214,748,364.8 to 214,748,364.7 µm
    -21,474.83648 to 21,474.83647 inches
    0 to 359.99999 degrees
    -2,147,483,648 to 2,147,483,647 pulses
    Increment-214,748,364.8 to 214,748,364.7 µm
    -21,474.83648 to 21,474.83647 inches
    -21,474.83648 to 21,474.83647 degrees
    -2,147,483,648 to 2,147,483,647 pulses
    Speed/Position Switching Control (INC Mode) / Position/Speed Switching Control0 to 214,748,364.7 µm
    0 to 21,474.83647 inches
    0 to 21,474.83647 degrees
    0 to 2,147,483,647 pulses
    Speed/Position Switching Control (ABS Mode)0 to 359.99999 degree
    Speed Command0.01 to 20,000,000.00 mm/min
    0.001 to 2,000,000.000 inch/min
    0.001 to 2,000,000.000 degree/min
    1 to 4,000,000 pulse/s
    Acceleration/Deceleration ProcessingTrapezoidal acceleration/deceleration, sigmoid acceleration/deceleration
    Acceleration/Deceleration Time1 to 8,388,608 ms
    Four patterns can be set for acceleration time and another 4 for deceleration time
    Quick Stop and Deceleration Time1 to 8,388,608 ms
    Starting Time1‑axis Linear Control1.5 ms
    1‑axis Speed Control1.5 ms
    2‑axis Linear Interpolation Control (Composite Speed)1.5 ms
    2‑axis Linear Interpolation Control (Reference Axis Speed)1.5 ms
    2‑axis Circular Interpolation Control2.0 ms
    2‑axis Speed Control1.5 ms
    3‑axis Linear Interpolation Control (Composite Speed)1.7 ms
    3‑axis Linear Interpolation Control (Reference Axis Speed)1.7 ms
    3‑axis Helical Interpolation Control2.6 ms
    3‑axis Speed Control1.7 ms
    4‑axis Linear Interpolation Control1.8 ms
    4‑axis Speed Control1.8 ms
    Factors for Extended Starting TimeIf any of the following conditions are met, the starting time is increased by the applicable time specified below.
    · Sigmoid acceleration/deceleration selected: 0.1 ms
    · Other axis operating: 0.5 ms
    · Continuous positioning control: 0.3 ms
    · Continuous path control: 0.3 ms
    Pulse Output SystemOpen collector output
    Maximum Output Pulse200 k pulse/s
    Maximum Connected Distance Between Servos2 m
    External Wiring Connection Method-40-pin connector × 2
    Compatible ConnectorA6CON1, A6CON2, A6CON4 (sold separately)
    Number of Occupied Input/Output32 points (I/O assignment: intelligent 32 points)
    5 V DC Internal Current Consumption0.55 A
    External DimensionsHeight (H)90 mm
    Width (W)45 mm
    Depth (D)95 mm
    Weight0.18 kg