MELSEC-F Series Data Link / Communication Unit

:
MITSUBISHI

    CC-Link system interface / master block.
    [Features]
    · Can connect to open networks.
    · Special expansion block to connect the sequencer to CC-Link.
    [Applications]
    · Interface to connect an FX sequencer as the CC-Link master / remote device station.

    CC-Link System Interface Block (Remote Device Station) FX2N-32CCL Features

    FX sequencers can be connected as a CC-Link remote device station.
    This permits distributed control and centralized management of lines.

    FX2N-32CCL Performance Specifications

    CC-Link VersionVer. 1.00
    Station TypeRemote device station
    Insulation MethodThe network bus and the internal power supply are insulated by a opto-isolator
    Transmission SpeedSelectable from 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps (set with a rotary switch)
    Station Number1 to 64 stations (set with a rotary switch)
    Number of Occupied Stations1 to 4 stations (set with a rotary switch)
    Maximum Total Cable Extension (Maximum Transmission Distance)Maximum 1,200 m; varies depending on the transmission speed
    Number of Remote Inputs/OutputsThere are 32 remote input points and 32 remote output points per station.
    Note that the upper 16 points of the last station are occupied by the CC-Link system as the system area.
    Number of Remote Register PointsThere are 4 remote register points in the RW write area, and 4 remote register points in the RW read area, per station.
    Link Points Per Station32 remote input points / 32 remote output points (RX/RY)
    Note that the upper 16 points of the last station are occupied by the CC-Link system as the system area.
    4 remote register (RWw) points (Master station > Remote device station)
    4 remote register (RWr) points (Remote device station > Master station)
    Communication MethodPolling method
    Synchronization MethodFrame synchronization method
    Encryption MethodNRZI method
    Transmission Path TypeBus (RS-485)
    Transmission FormatHDLC-compliant
    Error Control MethodCRC(X16 + X12 + X5 + 1)
    Connection CableDedicated CC-Link cable, dedicated CC-Link high-performance cable
    The dedicated CC-Link cable and dedicated CC-Link high-performance cable cannot be used at the same time.
    Communication With SequencersCommunication is performed using FROM/TO commands via buffer memory
    Display (LED)RD, SD, L RUN, L ERR, POWER
    Number of Occupied Inputs/Outputs8 points (may be counted using either input or output)
    Applicable SequencersFX1N, FX3G, FX2N, FX3U, FX1NC, FX3GC, FX2NC, FX3UC
    "Connection to connector type sequencer"
    FX2NC-CNV-IF is required to connect to the FX1NC or FX2NC.
    Either FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect to the FX3GC or FX3UC.
    Weight0.2 kg

    FX2N-32CCL Power Supply Specifications

    Power Supply5 V DC internal power supply: Energized from the sequencer via an extension cable.
    24 V DC external power supply (24 V DC ± 10%): Energized from the external terminal block.
    Current Consumption5 V DC internal power supply: 130 mA
    24 V DC external power supply: 50 mA

    CC-Link System Interface Block FX3U-64CCL Features

    The FX3U-64CCL type CC-Link interface block is a special expansion block for connecting an FX5U/FX5UC CPU unit or FX3G/FX3U/FX3GC/FX3UC sequencer to CC-Link. (Compatible with CC-Link V2)
    The FX3U-64CCL operates as an intelligent device station over CC-Link.
    Only one FX3U-64CCL unit can be connected to one sequencer base unit.
    The GX Developer can be used to access an FX5U/FX5UC CPU unit or FX3G/FX3U/FX3GC/FX3UC sequencer base unit to which the FX3U-64CCL is connected, from the Q master station / local station via CC-Link. (GX Developer of Ver. 8.76E or later is supported)

    FX3U-64CCL Performance Specifications

    CC-Link VersionVer. 2.00 (Ver. 1.10 is also supported)
    Station TypeIntelligent device station
    Insulation MethodThe network bus and the internal power supply are insulated by a opto-isolator
    Transmission SpeedSelectable from 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps
    Selectable (Set with a rotary switch.)
    Station Number1 to 64 stations (set with a rotary switch)
    Number of Occupied Stations1 to 4 stations (set with a rotary switch)
    Maximum Total Cable Extension (Maximum Transmission Distance)According to the CC-Link specification.
    Number of Remote Inputs/OutputsThere are 32 remote input points and 32 remote output points per station. (Expanded cyclic settings of × 1 to × 8 are available)
    Note that the upper 16 points of the last station are occupied by the CC-Link system as the system area.
    Number of Remote Register PointsThere are 4 remote register points in the RW write area, and 4 remote register points in the RW read area, per station.
    (Expanded cyclic settings of × 1 to × 8 are available)
    Communication MethodBroadcast polling method
    Synchronization MethodFlag synchronization method
    Encryption MethodNRZI method
    Transmission Path TypeBus (RS-485)
    Transmission FormatHDLC-compliant
    Error Control MethodCRC(X16 + X12 + X5 + 1)
    Connection CableDedicated CC-Link cable, dedicated CC-Link high-performance cable and dedicated CC-Link cable compatible with Ver. 1.10
    Different cables cannot be used at the same time.
    Communication With SequencersCommunication is performed using FROM/TO commands via buffer memory (or based on direct specification of buffer memory)
    Display (LED)RD, SD, RUN, ERR., L RUN, L ERR., POWER
    Number of Occupied Inputs/Outputs8 points (may be counted using either input or output)
    Applicable SequencersFX5U, FX5UC, FX3G, FX3U, FX3GC, FX3UC (Ver. 2.20 SER No.55**** Units produced in or after May 2005)
    * Only one 64CCL unit can be connected to one sequencer base unit.
    "Connection to FX5U and FX5UC CPU units"
    Either FX5-CNV-BUS or FX5-CNV-BUSC is required to connect to the FX5U or FX5UC.
    Select either one according to the system configuration.
    "Connection to connector type sequencer"
    Either FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect to the FX3GC and FX3UC.
    Weight0.3 kg

    FX3U-64CCL Power Supply Specifications

    Power Supply5 V DC internal power supply: 5 V DC from the sequencer is not used. (5 V DC is converted from a 24 V DC external power supply)
    24 V DC external power supply: Energized from the external terminal block. (+20%, -15%; ripple ratio (p-p): within 5%)
    Allowable Momentary Power Outage DurationPS1: Operation continues after a momentary power outage of 1 ms or less
    Current Consumption220 mA

    CC-Link System Master Block FX3U-16CCL-M Features

    Special expansion block to use FX5U/FX5UC CPU unit or FX3G/FX3U/FX3GC/FX3UC sequencer as the CC-Link master station.
    Up to 8 remote I/O stations and up to 8 remote device stations or intelligent device stations can be connected to the master station. (Up to 4 stations available for FX3G/FX3GC sequencer)
    By using the FX3U-16CCL-M type CC-Link master block and the FX3U-64CCL type CC-Link interface block, a CC-Link V2 system can be configured using only FX sequencers.

    FX3U-16CCL-M Performance Specifications

    CC-Link VersionVer. 2.00 (Ver. 1.10 is also supported)
    Station TypeMaster station (no local station or standby master station function)
    Transmission SpeedSelectable from 156 kbps / 625 kbps / 2.5 Mbps / 5 Mbps / 10 Mbps (set with a rotary switch)
    Station NumberNo. 0 (set with a rotary switch)
    Maximum Total Cable Extension
    (Maximum Transmission Distance)
    Maximum 1,200 m; varies depending on the transmission speed
    Maximum Number of Connected StationsRemote I/O StationsUp to 8 stations (actual 32 input/output points of sequencer are occupied per station)
    Total of Remote Device
    Stations + Intelligent
    Device Stations
    Up to 8 stations (total points for each of RX or RY shall be 256 or less)
    Maximum Input/Output Points Per System
    FX3U/FX3UC Sequencer
    Total of 1) + 2) below ≤ 384 points
    1) (Actual number of sequencer input/output points) + (Number of occupied special expansion block input/output points) + (Number of occupied 16CCL-M input/output points: 8 points) ≤ 256 points
    2) 32 × Number of remote I/O stations ≤ 256 points
    FX3G/FX3GC Sequencer
    32 × Number of remote I/O stations ≤ 128 points
    Link Points Per StationRemote inputs/outputs (RX, RY): 32 points
    Remote registers (RWw): 4 points (Master station > Remote device station / intelligent device station)
    Remote registers (RWr): 4 points (Remote device station / intelligent device station > Master station)
    *The above are the number of link points in the Remote Net Ver. 1 mode.
    Communication MethodBroadcast polling method
    Synchronization MethodFrame synchronization method
    Encryption MethodNRZI method
    Transmission Path TypeBus (RS-485)
    Transmission FormatHDLC-compliant
    Error Control MethodCRC(X16 + X12 + X5 + 1)
    Connection CableDedicated CC-Link cable / Dedicated CC-Link high-performance cable / Dedicated CC-Link cable compatible with Ver. 1.10
    Using the dedicated CC-Link cable, dedicated CC-Link high-performance cable and dedicated CC-Link cable compatible with Ver. 1.10 cannot be done at the same time.

    Also, install a terminating resistor corresponding to the type of cable.
    RAS Function· Auto-reset function
    · Slave-station isolation function
    · Error detection by special link relay / register
    Communication With SequencersCommunication is performed via buffer memory using FROM/TO commands or direct specification of buffer memory (FX3U/FX3UC), etc.
    Display (LED)RUN, ERR., L RUN, L ERR. , SD, RD, POWER
    Number of Occupied Inputs/Outputs8 points (may be counted using either input or output)
    Applicable SequencersFX5U, FX5UC, FX3G, FX3U (Ver. 2.20 or later), FX3GC, FX3UC (Ver. 2.20 or later)
    Using the FX3U-16CCL-M and FX2N-16CCL-M at the same time cannot be done with the FX2N-32ASI-M.
    The FX3U-16CCL-M and FX2N-16CCL-M cannot be used together.
    "Connection to FX5U and FX5UC CPU units"
    Either FX5-CNV-BUS or FX5-CNV-BUSC is required to connect to the FX5U or FX5UC.
    Select either one according to the system configuration.
    "Connection to connector type sequencer"
    Either FX2NC-CNV-IF or FX3UC-1PS-5V is required to connect to the FX3GC and FX3UC.
    Weight0.3 kg

    FX3U-16CCL-M Power Supply Specifications

    Power SupplyExternal Power Supply24 V DC +20%, -15%; ripple (p-p): within 5%
    Internal Power Supply5 V
    5 V DC from the sequencer is not used.
    (5 V DC is converted from the 24 V DC external power supply for energization)
    Follow the power input timing and procedure.
    Current Consumption24 V DC external power supply: 240 mA