CC-Link Space Optical Repeater

:
MITSUBISHI

    Space optical repeater unit that extends the maximum CC-Link distance.
    [Features]
    · Optical repeater unit for general-purpose sequencers.
    · Communication with a linear movement body.
    [Applications]
    · Network communication.

    CC-Link Repeater Unit Space Optical Repeater Unit Specifications

    CC-Link space optical repeater: related image

    AJ65BT-RPI-10A/AJ65BT-RPI-10B external appearance

    CC-Link space optical repeater: related image

    AJ65BT-RPI-10A/AJ65BT-RPI-10B dimensional drawing (unit: mm)

    Product NameType NameContentsNumber of Occupied PointsStation Type
    Space optical repeater unitAJ65BT-RPI-10AAJ65BT-RPI-10A and AJ65BT-RPT-10B are used as a set
    Compatible with 156 k / 625 k / 2.5 Mbps,
    Spatial transmission from 0 to 100 m with infrared rays
    Optical communication status monitor function
    -/1Remote I/O with one station occupied
    AJ65BT-RPI-10B-/1Remote I/O with one station occupied

    Common Items

    Optical Communication Specifications-
    Optical Transmission Distance0 to 100 m
    Direction AngleWhen the optical transmission distance is from 0 to 50 m: full angle of 2°
    When the optical transmission distance is from 50 to 100 m: full angle of 1°
    Modulation FrequencyA unit → B unit: 36 ±3 MHz
    B unit → A unit: 44 ±2.5 MHz
    Modulation MethodFSK
    CC-Link Specifications-
    Transmission Speed156 kbps / 625 kbps/ 2.5 Mbps (selectable)
    Maximum Number of Segment Connection StagesAJ65BT-RPI only: 2 stages
    Combination of AJ65BT-RPI and AJ65SBT-RPT: 3 stages
    Combination of AJ65BT-RPI, AJ65SBT-RPS, AJ65SBT-RPG, AJ65FBTA-RPH and AJ65BTS-RPH: 2 stages
    Maximum Transmission Distance of Each SegmentVaries depending on the transmission speed
    Maximum Number of Connected Devices64 devices
    Number of Occupied StationsMonitor function used: 1 station
    Monitor function not used: 0 station
    Dielectric StrengthBetween all DC external terminals and earth: 500 V AC for 1 minute
    Insulation ResistanceBetween all DC external terminals and earth: 10 MΩ or more at 500 V DC on an ohmmeter
    Unit Power SupplyVoltage20.4 to 26.4 V DC
    Current137 mA (when TYP. 24 V DC)
    External DimensionsHeight (H)100.0 mm
    Width (W)161.0 mm
    Depth (D)57.5 mm
    Weight0.5 kg
    Operating Ambient Temperature0 to 50°C
    Storage Ambient Temperature-20 to 75°C
    Operating Ambient Humidity10 to 90% RH, no condensation
    Ambient Storage Humidity10 to 90% RH, no condensation
    Vibration ResistanceJIS B 3502, IEC 61131-2 CompatibleUnder Intermittent VibrationFrequency: 5 to 8.4 Hz, single amplitude: 3.5 mm
    Frequency: 8.4 to 150 Hz, constant acceleration: 9.8 m/s2
    Sweeps: 10 sweeps in each direction of X, Y and Z
    Under Continuous VibrationFrequency: 5 to 8.4 Hz, single amplitude: 1.75 mm
    Frequency: 8.4 to 150 Hz, constant acceleration: 4.9 m/s2
    Impact ResistanceJIS B 3502, IEC 61131-2 compatible (490 m/s2, 10 times in 3 directions of X, Y and Z)
    Operating AtmosphereThere shall be no significant amount of dust and no corrosive gas
    Ambient Illuminance10,000 lx or less (not subject to direct sunlight)
    Cooling MethodSelf-cooling
    Operating Altitude0 to 2,000 m
    Installation LocationIndoors
    Overvoltage CategoryII or less
    Pollution Degree2 or less