(!) Since support from Microsoft will end on January 14th, 2020, Windows 7 will be excluded from the recommended environment from December 15th, 2019 on this site. Vì lý do Microsoft kết thúc hỗ trợ cho Windows 7 vào ngày 14/01/2020, Windows 7 sẽ là hệ điều hành không được khuyến khích sử dụng với trang web này từ ngày 15/12/2019.
Select part number to Order Now/ Add to Cart
Caution
thận trọng
[Features]
· With a high temperature stability of ±0.1°C due to a precise temperature control method that uses an expansion valve and a temperature sensor.
· With a compact tank.
· Power supply: Single-phase 200 to 230 V AC.
· Set temperature range: 5 to 40°C.
· HRS-0□□-A: Air-cooled refrigeration type.
· HRS-0□□-W: Water-cooled refrigeration type.
HRS Series Air-Cooled Refrigeration Type external appearance
Model | HRS012-A□-20 | HRS018-A□-20 | HRS024-A□-20 | HRS030-A□-20 | HRS050-A□-20 | HRS060-A□-20 | ||
---|---|---|---|---|---|---|---|---|
Cooling Method | Air-cooled refrigeration type | |||||||
Refrigerant | R407C (HFC) | R410A (HFC) | ||||||
Refrigerant Charge (kg) | 0.35 | 0.36 | 0.36 | 0.57 | 0.65 | 0.85 | ||
Control Method | PID control | |||||||
Ambient Operating Temperature / Humidity / Altitude*1 *12 | Temperature: 5 to 40°C, High-temperature environment specification (optional): 5 to 45°C, Humidity: 30 to 70%, Altitude: less than 3,000 m | |||||||
Circulating Fluid System | Circulating Fluid*2 | Clear water, 15% ethylene glycol aqueous solution*4 | ||||||
Set Temperature Range*1 (°C) | 5 to 40 | |||||||
Cooling Capacity*3 (50/60 Hz) (W) | 1,100/1,300 | 1,700/1,900 | 2,100/2,400 | 2,600/3,200 | 4,700/5,100 | 4,900/5,900 | ||
Heating Capacity*3 (50/60 Hz) (W) | 530/650 | 600/640 | 1,100/1,400 | 1,000/1,300 | ||||
Temperature Stability*5 (°C) | ±0.1 | |||||||
Pump | Rated Flow Rate*6 *7 (50/60 Hz) (L/min) | 7 (0.13 MPa) / 7 (0.18 MPa) | 23 (0.24 MPa) / 28 (0.32 MPa) | 23 (0.21 MPa) / 28 (0.29 MPa) | ||||
Maximum Flow Rate (50/60 Hz) (L/min) | 27/29 | 34/40 | 31/42 | 29/38 | ||||
Maximum Pump Head (50/60 Hz) (m) | 14/19 | 50 | ||||||
Output (W) | 200 | 550 | ||||||
Tank Capacity (L) | Approx. 5 | |||||||
Pipe Connection Port Diameter | Rc 1/2 | |||||||
Fluid Contacting Parts Material | Stainless steel, copper (heat exchanger brazing), bronze, alumina ceramic, carbon, PP, PE, POM, FKM, EPDM, PVC | |||||||
Electrical Systems | Power Supply | Single-phase 200 to 230 V AC (50/60 Hz) Allowable voltage variation ±10% | ||||||
Circuit Protector (A) | 10 | 20 | 30 | |||||
Compatible Earth Leakage Circuit Breaker Capacity*8 (A) | 10 | 20 | 30 | |||||
Rated Operating Current (A) | 4.6/5.1 | 4.7/5.2 | 5.1/5.9 | 5.2/6.0 | 8/11 | 8.9/11.5 | ||
Rated Power Consumption*3 (50/60 Hz) (kVA) | 0.9/1.0 | 0.9/1.0 | 1.0/1.2 | 1.0/1.2 | 1.7/2.2 | 1.8/2.3 | ||
Noise Level*9 (50/60 Hz) (dB) | 60/61 | 62/65 | 65/68 | 66/68 | ||||
Accessories | Pipe fitting (for drain outlet) 1 pc.*11, Input/output signal connector 1 pc., Power supply connector 1 pc.*11 Operation manual (for installation and operation) 1 pc., Quick manual (with a clear case) 1 pc.*11 Alarm code list sticker 1 pc., ferrite core (for communication) 1 pc. Power cable must be purchased separately or provided by the user. | |||||||
Weight*10 (kg) | 43 | 47 | 69 | 73 |
*Some values differ from the standard specifications due to optional features. See the catalog for details.
*1: Use in a condensation-free environment.
*2: If you are using clear water, please use water that meets the Japan Refrigeration and Air Conditioning Industry Association Water Quality Standards (JRA GL-02-1994: Cooling Water / Circulation Type / Supply Water).
*3: Values when: 1. Ambient operating temperature: 25°C, 2. Circulating fluid temperature: 20°C, 3. Rated flow rate of circulating fluid, 4. Circulating fluid: clear water. See the cooling capacity graphs in the catalog for details.
*4: If the circulating fluid temperature is below 10°C, use 15% ethylene glycol aqueous solution.
*5: Outlet temperature when the circulating fluid is at rated flow rate, and the outlet and return port are connected. When the installation environment and power supply are within the specification range and stable.
*6: The capacity at the outlet of this device when the circulating fluid temperature is 20°C.
*7: Minimum flow rate required to maintain cooling capacity, temperature stability, etc. Below the rated flow rate, the cooling capacity and temperature stability may not meet specifications. (In that case, use a bypass piping set [sold separately].
*8: To be provided by the customer. Use an earth leakage circuit breaker with a current sensitivity of 30 mA. (An option with an earth leakage circuit breaker [symbol B] is also available.)
*9: When front 1 m, height 1 m, stable with no load. See *3 for other conditions.
*10: Weight in a dry state without circulating fluid.
*11: Not included with the HRS050/060.
*12: For altitudes above 1,000 m, please refer to "*For altitudes above 1,000 m" in Section 14 "Operating Environment and Storage Environment," on p. 64 of the catalog.
HRS Series Water-Cooled Refrigeration Type external appearance
Model | HRS012-W□-20 | HRS018-W□-20 | HRS024-W□-20 | HRS030-W□-20 | HRS050-W□-20 | HRS060-W□-20 | ||
---|---|---|---|---|---|---|---|---|
Cooling Method | Water-cooled refrigeration type | |||||||
Refrigerant | R407C (HFC) | R410A (HFC) | ||||||
Refrigerant Charge (kg) | 0.3 | 0.31 | 0.31 | 0.5 | 0.65 | 0.75 | ||
Control Method | PID control | |||||||
Ambient Operating Temperature / Humidity / Altitude*1 | Temperature: 5 to 40°C, Humidity: 30 to 70%, Altitude: Less than 3,000 m | |||||||
Circulating Fluid System | Circulating Fluid*2 | Clear water, 15% ethylene glycol aqueous solution*4 | ||||||
Set Temperature Range*1 (°C) | 5 to 40 | |||||||
Cooling Capacity*3 (50/60 Hz) (W) | 1,100/1,300 | 1,700/1,900 | 2,100/2,400 | 2,600/3,200 | 4,700/5,100 | 4,900/5,900 | ||
Heating Capacity*3 (50/60 Hz) (W) | 530/650 | 400/600 | 1,000/1,300 | |||||
Temperature Stability*5 (°C) | ±0.1 | |||||||
Pump | Rated Flow Rate*6 *7 (50/60 Hz) (L/min) | 7 (0.13 MPa) / 7 (0.18 MPa) | 23 (0.24 MPa) / 28 (0.32 MPa) | 23 (0.21 MPa) / 28 (0.29 MPa) | ||||
Maximum Flow Rate (50/60 Hz) (L/min) | 27/29 | 34/40 | 31/42 | 29/38 | ||||
Maximum Pump Head (50/60 Hz) (m) | 14/19 | 50 | ||||||
Output (W) | 200 | 550 | ||||||
Tank Capacity (L) | Approx. 5 | |||||||
Pipe Connection Port Diameter | Rc 1/2 | |||||||
Fluid Contacting Parts Material | Stainless steel, copper (heat exchanger brazing), bronze, alumina ceramic, carbon, PP, PE, POM, FKM, EPDM, PVC | |||||||
Heat-Dissipating Water System | Temperature Range (°C) | 5 to 40 | ||||||
Pressure Range (MPa) | 0.3 to 0.5 | |||||||
Required Flow Rate*11 (50/60 Hz) (L/min) | 8 | 12 | 14 | 15 | 16 | 17 | ||
Inlet-Outlet Pressure Differential of Heat-Dissipating Water (MPa) | 0.3 or more | |||||||
Pipe Connection Port Diameter | Rc3/8 | Rc 1/2 | ||||||
Fluid Contacting Parts Material | Stainless steel, copper (heat exchanger brazing), bronze, synthetic rubber | |||||||
Electrical Systems | Power Supply | Single-phase 200 to 230 V AC (50/60 Hz) Allowable voltage variation ±10% | ||||||
Circuit Protector (A) | 10 | 20 | ||||||
Compatible Earth Leakage Circuit Breaker Capacity*8 (A) | 10 | 20 | ||||||
Rated Operating Current (A) | 4.6/5.1 | 4.7/5.2 | 5.1/5.9 | 5.2/6.0 | 7.6/10 | 7.6/10.4 | ||
Rated Power Consumption Note 3) (50/60 Hz) kVA | 0.9/1.0 | 0.9/1.0 | 1.0/1.2 | 1.0/1.2 | 1.5/2.0 | 1.5/2.1 | ||
Noise Level*9 (50/60 Hz) (dB) | 60/61 | 62/65 | 65/68 | 66/68 | ||||
Accessories | Pipe fitting (for drain outlet) 1 pc.*12, Input/output signal connector 1 pc., Power supply connector 1 pc.*12 Operation manual (for installation and operation) 1 pc., Quick manual (with a clear case) 1 pc.*12 Alarm code list sticker 1 pc., ferrite core (for communication) 1 pc. Power cable must be purchased separately or provided by the user. | |||||||
Weight*10 (kg) | 43 | 46 | 67 |
*Some values differ from the standard specifications due to optional features. See the catalog for details.
*1: Use in a condensation-free environment.
*2: If you are using clear water, please use water that meets the Japan Refrigeration and Air Conditioning Industry Association Water Quality Standards (JRA GL-02-1994: Cooling Water / Circulation Type / Supply Water).
*3: Values when: 1. Ambient operating temperature: 25°C, 2. Circulating fluid temperature: 20°C, 3. Rated flow rate of circulating fluid, 4. Circulating fluid: clear water, 5. Heat-dissipating water temperature: 25°C. See the cooling capacity graphs in the catalog for details.
*4: If the circulating fluid temperature is below 10°C, use 15% ethylene glycol aqueous solution.
*5: Outlet temperature when the circulating fluid is at rated flow rate, and the outlet and return port are connected. When the installation environment and power supply are within the specification range and stable.
*6: The capacity at the outlet of this device when the circulating fluid temperature is 20°C.
*7: Minimum flow rate required to maintain cooling capacity, temperature stability, etc.
Below the rated flow rate, the cooling capacity and temperature stability may not meet specifications. (In that case, use a bypass piping set [sold separately].)
*8: To be provided by the customer. Use an earth leakage circuit breaker with a current sensitivity of 30 mA. (An option with an earth leakage circuit breaker [symbol B] is also available.)
*9: When front 1 m, height 1 m, stable with no load. See *3 for other conditions.
*10: Weight in a dry state without circulating fluid.
*11 Required flow rate when the circulating fluid temperature is 20°C, the circulating fluid is at the rated flow rate, the heat-dissipating fluid is 25°C and the listed cooling capacity load is applied.
*12: Not included with the HRS050/060.
HRS012/018-A/W-10 (single-phase 100/115 V AC) pump capacity
HRS-012/018/024-A/W-20 (single-phase 200 to 230 V AC) pump capacity
Mechanical seal details
Notes
*The pump used in the Thermo-Chiller HRS050/060 Series uses a mechanical seal with a fixed ring and a rotating ring in the shaft seal. If foreign matter enters the gap in the seal, it could cause issues such as seal leakage, pump lock, etc., so it is highly recommended that a particle filter is installed on the chiller return piping.
(Unit: mm)
HRS012/018/024 dimensions/diagram
HRS030-A-20 dimensions/diagram
HRS030-W-20 dimensions/diagram
HRS050/060-A dimensions/diagram
HRS050/060-W dimensions/diagram
Part Number |
---|
HRS050-A-20 |
Part Number | Price | Minimum Order Qty. | Volume Discount | Days to ShipSố ngày giao hàng | RoHS | Type | Cooling Method | Cooling capacity | Piping thread type | Optional specifications | Cooling method | Power Supply Specification |
---|---|---|---|---|---|---|---|---|---|---|---|---|
260,072,000 VND | 1 Piece(s) | 32 Day(s) | - | Thermo-Chiller | Air-Cooling | 4,700/5,100 W (50/60 Hz) | Rc | None | - | - |
Loading...Tải…
Please check the type/dimensions/specifications of the part HRS050-A-20 in the Thermo-Chiller Standard Type Single-Phase 200 to 230 V AC HRS Series series.Vui lòng kiểm tra kiểu/kích thước/thông số kỹ thuật của phần HRS050-A-20 trong chuỗi Thermo-Chiller Standard Type Single-Phase 200 to 230 V AC HRS Series.
Part Number |
---|
HRS012-A-20-BJMT |
HRS012-A-20-BJW |
HRS012-A-20-BM |
HRS050-A-20-B |
HRS050-A-20-BJMW |
HRS050-A-20-BJW |
Part Number | Standard Unit Price | Minimum order quantity | Volume Discount | Days to ShipSố ngày giao hàng | RoHS | Type | Cooling Method | Cooling capacity | Piping thread type | Optional specifications | Cooling method | Power Supply Specification |
---|---|---|---|---|---|---|---|---|---|---|---|---|
- | 1 Piece(s) | Quote | - | - | - | 1,100/1,300 W (50/60 Hz) | Rc | With earth leakage circuit breaker / With automatic water supply / Compatible with deionized water (pure water) piping / High pump head specification | - | - | ||
- | 1 Piece(s) | Quote | 10 | - | - | 1,100/1,300 W (50/60 Hz) | Rc | With earth leakage circuit breaker / with automatic water supply / SI unit only | Air-cooled refrigeration type | Single-phase 200 to 230 V AC (50/60 Hz) | ||
- | 1 Piece(s) | Quote | - | - | - | 1,100/1,300 W (50/60 Hz) | Rc | With earth leakage circuit breaker / Compatible with deionized water (pure water) piping | - | - | ||
264,218,000 VND | 1 Piece(s) | 32 Day(s) | - | Thermo-Chiller | Air-Cooling | 4,700/5,100 W (50/60 Hz) | Rc | With earth leakage circuit breaker | - | - | ||
- | 1 Piece(s) | Quote | 10 | - | - | 4700/5100 W (50/60 Hz) | Rc | With earth leakage circuit breaker / with automatic water supply / for deionized water (pure water) piping / SI unit only | Air-cooled refrigeration type | Single-phase 200 to 230 V AC (50/60 Hz) | ||
- | 1 Piece(s) | Quote | 10 | - | - | 4700/5100 W (50/60 Hz) | Rc | With earth leakage circuit breaker / with automatic water supply / SI unit only | Air-cooled refrigeration type | Single-phase 200 to 230 V AC (50/60 Hz) |
How can we improve?
How can we improve?
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Customer Privacy Policy
Thank you for your cooperation.
While we are not able to respond directly to comments submitted in this form, the information will be reviewed for future improvement.
Please use the inquiry form.
Customer Privacy Policy